In the electricity sector in the United Kingdom, the National Grid is the high-voltage electric power transmission network serving Great Britain, connecting power stations and major substations and ensuring that electricity generated anywhere on it can be used to satisfy demand elsewhere. The network covers the great majority of Great Britain and several of the surrounding islands. It does not cover Northern Ireland, which is part of a single electricity market with the Republic of Ireland.

400 kV power line in Cheshire

The GB grid is connected as a wide area synchronous grid nominally running at 50 hertz. There are also undersea interconnections to other grids in the Isle of Man, Northern Ireland, the Republic of Ireland, France, Belgium, the Netherlands and Norway.

On the breakup of the Central Electricity Generating Board in 1990, the ownership and operation of the National Grid in England and Wales passed to National Grid Company plc, later to become National Grid Transco, and now National Grid plc. In Scotland the grid was already split into two separate entities, one for southern and central Scotland and the other for northern Scotland, with interconnectors. The first is owned and maintained by SP Energy Networks, a subsidiary of Scottish Power, and the other by SSE. However, National Grid plc continues to be the transmission system operator for the whole GB grid.[1]

History

 
Electricity pylons in a suburban area of Pudsey, West Yorkshire

At the end of the 19th century, Nikola Tesla established the principles of three-phase high-voltage electric power distribution while he was working for Westinghouse in the United States.[2][3] The first use of this system in the United Kingdom was by Charles Merz, of the Merz & McLellan consulting partnership, at his Neptune Bank Power Station near Newcastle upon Tyne. This opened in 1901,[4] and by 1912 had developed into the largest integrated power system in Europe.[5] The rest of the country, however, continued to use a patchwork of small supply networks.

In 1925, the British government asked Lord Weir, a Glaswegian industrialist, to solve the problem of Britain's inefficient and fragmented electricity supply industry. Weir consulted Merz, and the result was the Electricity (Supply) Act 1926, which recommended that a "national gridiron" supply system be created.[6] The 1926 Act created the Central Electricity Board, which set up the UK's first synchronised, nationwide AC grid, running at 132 kV, 50 Hz.

 
National Grid helicopter inspecting overhead cables in Greater Manchester

The grid was created with 6,400 kilometres (4,000 mi) of cables – mostly overhead – linking the 122 most efficient power stations. The first "grid tower" was erected near Edinburgh on 14 July 1928,[7] and work was completed in September 1933, ahead of schedule and on budget.[8][9] It began operating in 1933 as a series of regional grids with auxiliary interconnections for emergency use. Following the unauthorised but successful short term parallelling of all regional grids by the night-time engineers on 29 October 1937,[10] by 1938 the grid was operating as a national system. The growth by then in the number of electricity users was the fastest in the world, rising from three quarters of a million in 1920 to nine million in 1938.[9] The grid proved its worth during the Blitz, when South Wales provided power to replace lost output from Battersea and Fulham power stations.[9] The grid was nationalised by the Electricity Act 1947, which also created the British Electricity Authority. In 1949, the British Electricity Authority decided to upgrade the grid by adding 275 kV links.

At its inception in 1950, the 275 kV Transmission System was designed to form part of a national supply system with an anticipated total demand of 30,000 MW by 1970. The predicted demand was already exceeded by 1960. This rapid growth led the Central Electricity Generating Board (created in 1958) to carry out a study in 1960 of future transmission needs. The report was completed in September 1960, and its study is described in a paper presented to the Institution of Electrical Engineers by E. S. Booth, D. Clark, J. L. Egginton and J. S. Forrest in 1962.

Considered in the study, together with the increased demand, was the effect on the transmission system of the rapid advances in generator design resulting in projected power stations of 2,000–3,000 MW installed capacity. These new stations were mostly to be sited where advantage could be taken of a surplus of cheap low-grade fuel and adequate supplies of cooling water, but these sites did not coincide with the load centres. West Burton's 4 × 500 MW machines, in the Nottinghamshire coalfield near the River Trent, is an example. These developments shifted the emphasis on the transmission system from interconnection to bulk power transfers from the generation areas to the load centres, such as the anticipated transfer in 1970 of some 6,000 MW from the Midlands to the home counties.

Continued reinforcement and extension of the 275 kV systems was examined as a possible solution. However, in addition to the technical problem of high fault levels, many more lines would have been required to obtain the estimated transfers at 275 kV. As this was not consistent with the Central Electricity Generating Board's policy of preservation of amenities, a better solution was sought. Consideration was given to 400 kV and 500 kV schemes: both gave a sufficient margin for future expansion. The decision in favour of a 400 kV system was made for two main reasons. Firstly the majority of the 275 kV lines could be uprated to 400 kV, and secondly it was envisaged that operation at 400 kV could begin in 1965 compared with 1968 for a 500 kV scheme. Design work was started and in order to meet the programme for 1965 it was necessary for the contract engineering for the first projects to run concurrently with the design. One of these projects was the West Burton 400 kV Indoor Substation, the first section of which was commissioned in June 1965. From 1965, the grid was partly upgraded to 400 kV, beginning with a 150-mile (240 km) line from Sundon to West Burton, to become the Supergrid.

In the 2010 issue of the code that governs the National Grid, the Grid Code,[11] the Supergrid is defined as those parts of the British electricity transmission system that are connected at voltages in excess of 200 kV.

The 2.2 GW undersea Western HVDC Link from Scotland to North Wales was built in 2013–2018.[12] This was the first major non-alternating current grid link within Great Britain, although interconnectors to foreign grids already used HVDC.

In 2021 a new non-lattice design of electricity pylon, the T-pylon, was built near East Huntspill, Somerset for the new 35 mile Hinkley Point C to Avonmouth connection.[13]

Characteristics of the grid

 
UK electricity production by source 1985–2020[14][15][16][17][18]
 
Electricity supplied (net) 1920–2014[19]
External images
  Current grid status, charts
  Current grid status, dials

The contiguous synchronous grid covers England (including the Isle of Wight), Scotland (including some of the Scottish islands such as Orkney, Skye[20] and the Western Isles which have limited connectivity[21]), Wales, and the Isle of Man.

Network size

The following figures are taken from the 2005 Seven Year Statement.[22]

  • Maximum demand (2005/6): 63 GW (approx.) (81.39% of capacity)
  • Minimum demand (2020 May): 15.3 GW[23]
  • Annual electrical energy used in the UK is around 360 TWh (1.3 EJ)
  • Capacity (2005/6): 79.9 GW (or 80 GW per the 2008 Seven Year Statement)[24]
  • Number of large power stations connected to it: 181
  • Length of 400 kV grid: 11,500 km (circuit)
  • Length of 275 kV grid: 9,800 km (circuit)
  • Length of 132 kV (or lower) grid; 5,250 km (circuit)

Total generating capacity is supplied roughly equally by renewable, gas fired, nuclear, coal fired power stations. Annual energy transmitted in the UK grid is around 300–360 TWh (1.1–1.3 EJ), with an average load factor of 72% (i.e. 3.6×1011/(8,760 × 57×106).[needs update]

Decarbonisation

The national grid has a stretch target to be carbon neutral or negative by 2033, well ahead of the UK's national target to achieve this by 2050. It also aims to have the capability to be 'zero carbon' as early as 2025, meaning that if energy suppliers are able to produce sufficient green power, the grid could theoretically run without any greenhouse gas emissions at all (i.e. no carbon capture or offsetting would be needed as is the case with 'net zero').[25] In 2020 about 40% of the grid's energy came from burning natural gas, and it is not expected that anywhere close to sufficient green power will be available to run the grid on zero carbon in 2025, except perhaps on the very windiest days. Analysts such as Hartree Solutions considered in 2020 that getting to 'net zero' by 2050 would be challenging, even more so to reach 'net zero' by 2033. There has, however, been sustained progress towards carbon neutrality, with carbon intensity falling by 53% in the five years to 2020. The phase out of coal is progressing rapidly with only 1.6% of the UK's electricity coming from coal in 2020, compared with about 25% in 2015. 2020 saw the UK go more than two months without needing to burn any coal for electricity, the longest period since the industrial revolution.[26][27][28][29][30][31]

Losses

Figures are again from the 2005 Seven Year Statement.

  • Joule heating in cables: 857.8 MW
  • Fixed losses: 266 MW (consists of corona and iron loss; can be 100 MW higher in adverse weather)
  • Substation transformer heating losses: 142.4 MW
  • Generator transformer heating losses: 157.3 MW
  • Total losses: 1,423.5 MW (2.29% of peak demand)

Although overall losses in the national grid are low, there are significant further losses in onward electricity distribution to the consumer, causing a total distribution loss of about 7.7%.[citation needed] Losses differ significantly for customers connected at different voltages; connected at high voltage the total losses are about 2.6%, at medium voltage 6.4% and at low voltage 12.2%.[32]

Generated power entering the grid is metered at the high-voltage side of the generator transformer.[33][34] Any power losses in the generator transformer are therefore accounted to the generating company, not to the grid system. The power loss in the generator transformer does not contribute to the grid losses.

Power flow

In 2009–10 there was an average power flow of about 11 GW from the north of the UK, particularly from Scotland and northern England, to the south of the UK across the grid. This flow was anticipated to grow to about 12 GW by 2014.[35] Completion of the Western HVDC Link in 2018 added capacity for a flow of 2.2 GW between Western Scotland and North Wales.[36]

Because of the power loss associated with this north to south flow, the effectiveness and efficiency of new generation capacity is significantly affected by its location. For example, new generating capacity on the south coast has about 12% greater effectiveness due to reduced transmission system power losses compared to new generating capacity in north England, and about 20% greater effectiveness than in northern Scotland.[37]

Interconnectors

 
  Existing links
  Under construction
  Proposed
Some of these HVDC lines transfer power from renewable sources such as hydro and wind. For names, see also the annotated version.[needs update]

There is a 40 MW AC cable to the Isle of Man, the Isle of Man to England Interconnector.

The UK grid is connected to adjacent European electrical grids by submarine power cables at an electricity interconnection level (transmission capacity relative to production capacity) which was 6% as of 2014.[38]

As of 2022, the total capacity of these connectors is about 7.7 GW.[citation needed] They include direct-current cables to northern France (2 GW HVDC Cross-Channel, 1 GW HVDC IFA-2, 1 GW ElecLink via the Channel Tunnel[39]); Belgium (1 GW HVDC Nemo Link); the Netherlands (1 GW HVDC BritNed); Norway (1.4 GW HDVC North Sea Link); Northern Ireland (500 MW HVDC Moyle Interconnector); and the Republic of Ireland (500 MW HVDC East–West Interconnector).

A link is under construction to Denmark (1.4 GW Viking Link) which is due to be completed in 2023. A further 500 MW link with the Republic of Ireland (Greenlink) is scheduled for 2024.[40] Further potential schemes include links with Germany (NeuConnect, 1.4 GW); Iceland (Icelink, around 1 GW)[41] and Morocco (3.6 GW from new battery-backed solar generation).[42]

Grid storage

The UK grid has access to large pumped storage systems, notably Dinorwig Power Station which can provide 1.7 GW for 5–6 hours, and the smaller Cruachan and Ffestiniog.

There are also some grid batteries. As of May 2021, 1.3 GW of battery storage was operating in the United Kingdom, with 16 GW of projects in the pipeline potentially deployable over the next few years.[43] A 100 MW power Chinese-financed plant at Minety, Wiltshire was reported to be the largest in Europe when it opened in July 2021;[44] when a 50 MW extension is completed, the site's storage capacity will be 266 MWh.[45]

Reserve services and frequency response

National Grid is responsible for contracting short term generating provision to cover demand prediction errors and sudden failures at power stations. This covers a few hours of operation giving time for market contracts to be established to cover longer term balancing.

Frequency-response reserves act to keep the system's AC frequency within ±1% of 50 Hz, except in exceptional circumstances. These are used on a second by second basis to either lower the demand or to provide extra generation.[46]

Reserve services are a group of services each acting within different response times:[46]

  • Fast Reserve: rapid delivery (within two minutes) of increased generation or reduced demand, sustainable for a minimum of 15 minutes.
  • Fast Start: generation units that start from a standstill and deliver power within five minutes automatically, or within seven minutes of a manual instruction, with generation maintained for a minimum of four hours.
  • Demand Management: reduction in demand of at least 25 MW from large power users, for at least an hour.
  • Short Term Operating Reserve (STOR): generation of at least 3 MW, from a single or aggregation of sites, within four hours of instruction and maintained for at least two hours.
  • BM Start-Up: mainstream major generation units maintained in either an energy readiness or hot standby state.

These reserves are sized according to three factors:[47]

  • The largest credible single generation failure event, which is currently either Sizewell B nuclear power station (1,260 MW) or one cable of the HVDC Cross-Channel interconnector (1,000 MW)
  • The general anticipated availability of all generation plants
  • Anticipated demand prediction errors

Control of the grid

The English and Welsh parts of the National Grid are controlled from the National Grid Control Centre which is located in St Catherine's Lodge, Sindlesham, Wokingham in Berkshire.[48][49][50][51] It is sometimes described as being a 'secret' location.[52] As of 2015 the system is under consistent cyber attack.[53]

Although the transmission network in Scotland is owned by separate companies – SP Transmission plc (part of Scottish Power) in the south, and Scottish Hydro Electric Transmission plc (part of Scottish and Southern Electricity Networks) in the north[54] – overall control rests with National Grid Electricity System Operator.[1]

Transmission costs

The costs of operating the National Grid System are recouped by National Grid Electricity System Operator (NGESO) through levying of Transmission Network Use of System (TNUoS) charges on the users of the system.[55] The costs are split between the generators and the users of electricity.[56]

Tariffs are set annually by NGESO, and the country is divided into zones, each with a different tariff for generation and consumption. In general, tariffs are higher for generators in the north and consumers in the south since there is generally a north–south flow of electricity.

Triad demand

'Triad demand' is a metric of demand which reports retrospectively three numbers about peak demand between November and February (inclusive) each winter. In order to encourage usage of the National Grid to be less 'peaky', the triad is used as the basis for extra charges paid by the users (the licensed electricity suppliers) to the National Grid: the users pay less if they can manage their usage so as to be less peaky.

For each year's calculation, historic system demand metrics are analysed to determine three half-hour periods of high average demand; the three periods are known as triads. The periods are (a) the period of peak system demand, and (b) two other periods of highest demand which are separated from peak system demand and from each other by at least ten days.

For power stations, the chargeable demand is only the net site demand (per CUSC rule 14.17.10), so when the site is net exporting (i.e. total metered generation at that site exceeds total separately-metered station demand), that separately-metered station demand shall not be liable for demand TNUoS charges in relation to the station demand at triad.

Triad dates in recent years were:

Year Triad 1 Triad 2 Triad 3
2015/16 [57] Wednesday 25 November 2015, 17:00 – 17:30 Tuesday 19 January 2016, 17:00–17:30 Monday 15 February 2016, 18:00–18:30
2016/17 [58] Monday 5 December 2016, 17:00 – 17:30 Thursday 5 January 2017, 17:00 – 17:30 Monday 23 January 2017, 17:00 – 17:30
2017/18 [59] Monday 11 December 2017, 17:30 – 18:00 Monday 26 February 2018, 18:30–19:00 Monday 5 February 2018, 18:00–18:30
2018/19
2019/20
2020/21 [60] Monday 7 December 2020, 17:00 - 17:30 Thursday 7 January 2021, 17:30 - 18:00 Wednesday 10 February 2021, 18:00 - 18:30

In April of each year, each licensed electricity supplier (such as Centrica, BGB, etc.) is charged a yearly fee for the load it imposed on the grid during those three half-hours of the previous winter. Exact charges vary depending on the distance from the centre of the network, but in the South West it is £21,000/MW.[citation needed] The average for the whole country is about £15,000/MW. This is a means for National Grid to recover some of its costs, and to impose an incentive on users to minimise consumption at peak, thereby easing the need for investment in the system. It is estimated that these charges reduced peak load by about 1 GW out of say 57 GW.[citation needed]

This is the main source of income which National Grid uses to cover its costs for high-voltage long-distance transmission (lower voltage distribution is charged separately). The grid also charges an annual fee to cover the cost of generators, distribution networks and large industrial users connecting.

Triad charges encourage users to cut load at peak periods; this is often achieved by using diesel generators. Such generators are also routinely used by National Grid.[61]

Estimating costs per kW⋅h of transmission

If the total TNUoS or Triad receipts (say £15,000/MW·year × 50,000 MW = £750 million/year) is divided by the total number of units delivered by the UK generating system in a year (the total number of units sold – say 360 terawatt-hours (1.3 EJ).[56]), then a crude estimate can be made of transmission costs, and one gets the figure of around 0.2p/kW⋅h. Other estimates also give a figure of 0.2p/kW⋅h.[56]

However, Bernard Quigg notes: "According to the 06/07 annual accounts for NGC UK transmission, NGC carried 350TW⋅h for an income of £2012m in 2007, i. e. NGC receives 0.66p per kW hour. With two years inflation to 2008/9, say 0.71p per kW⋅h.",[62] but this also includes generators' connection fees.

Generation charges

In order to be allowed to supply electricity to the transmission system, generators must be licensed (by BEIS) and enter into a connection agreement with NGET which also grants Transmission Entry Capacity (TEC). Generators contribute to the costs of running the system by paying for TEC, at the generation TNUoS tariffs set by NGET. This is charged on a maximum-capacity basis. In other words, a generator with 100 MW of TEC who only generated at a maximum rate of 75 MW during the year would still be charged for the full 100 MW of TEC.[citation needed]

In some cases, there are negative TNUoS tariffs. These generators are paid an amount based on their peak net supply over three proving runs over the course of the year. This represents the reduction in costs caused by having a generator close to the centre of demand of the country.[citation needed]

National Grid uses a grid services market. "Dynamic Containment" started in October 2020, initially priced at £17 per MW per hour, and Dynamic Regulation (DR) started in April 2022.[63]

Demand charges

Consumers of electricity are split into two categories: half-hourly metered (HH) and non-half-hourly metered (NHH). Customers whose peak demand is sufficiently high are obliged to have a HH meter, which, in effect, takes a meter reading every 30 minutes. The rates at which charges are levied on these customers' electricity suppliers therefore varies 17,520 times a (non-leap) year.

The TNUoS charges for a HH metered customer are based on their demand during three half-hour periods of greatest demand between November and February, known as the Triad. Due to the nature of electricity demand in the UK, the three Triad periods always fall in the early evening, and must be separated by at least ten clear working days. The TNUoS charges for a HH customer are simply their average demand during the triad periods multiplied by the tariff for their zone. Therefore, (as of 2007) a customer in London with a 1 MW average demand during the three triad periods would pay £19,430 in TNUoS charges.

TNUoS charges levied on NHH metered customers are much simpler. A supplier is charged for the sum of their total consumption between 16:00 and 19:00 every day over a year, multiplied by the relevant tariff.

Constraint payments

Constraint payments are payments to generators above a certain size, where the National Grid gives them dispatch instructions that they are unable to take the electricity that the generators would normally provide. This can be due to a lack of transmission capacity, a shortfall in demand, or unexpected excess generation. A constraint payment is recompense for the reduction in generation.[64]

Major incidents

Power cuts because of problems with the infrastructure of the Supergrid or lack of generation to supply it with sufficient power are very rare. The nominal standard of security of supply is for power cuts due to lack of generation to occur in nine winters in a hundred.

The overall performance measure for electricity transmission is published on NGET's website[65] and includes a simple high-level figure on transmission availability and reliability of supply. For 2008–9 this was 99.99979%. Issues affecting the low voltage distribution systems – for which National Grid is not responsible – cause almost all the 60 minutes or so per year, on average, of domestic power cuts. Most of these low voltage distribution interruptions are in turn the fault of third parties such as workmen drilling through the street mains (or subterranean higher voltage) cables; this does not happen to major transmission lines, which are for the most part overhead on pylons. For comparison with Supergrid availability, Ofgem, the electricity regulator, has published figures on the performance of 14 electricity distributors.[66][67]

Since 1990, there have been three power cuts of high national prominence that were linked to National Grid, two due to generation issues.

August 2003

The first case was in August 2003, and related to the condition of National Grid's assets. In the early evening of 28 August, a power cut affected 476,000 customers in South London, as well as the London Underground and some rail services. Some news reports accused National Grid of under-investment in new assets at the time.

A transformer oil leak had been left untreated, except for top-ups, for many months, pending a proper fix. It also transpired that there was a significant error in a protection relay setting which became evident, resulting in a power cut, only when the first fault, the oil leak, had a real effect. National Grid took some time to admit to these aspects of the incident.[68][69]

A second event happened on 5 September 2003 which affected 220,000 customers in East Birmingham. This was attributed to an error made by National Grid when commissioning protection systems.[69]

May 2008

The second case was in May 2008, and related to generation issues for which National Grid was not responsible. A power cut took place in which a protective shutdown of parts of the network was undertaken by the distribution network operators, under pre-arranged rules, due to a sudden loss of generating capacity causing a severe drop in system frequency. First, two of Britain's largest power stations, Longannet in Fife and Sizewell B in Suffolk, shut down unexpectedly ('tripped') within five minutes of one another. There was no relationship between the two trips: the first did not cause the second. Such a loss is most unusual; at that time, Grid secured only against the loss of 1320 MW – the "infrequent infeed loss limit" (which rose to 1800 MW from 2014). The two shutdowns caused a sudden 1,510 MW adverse change in the balance of generation and demand on the Supergrid, and the frequency dropped to 49.2 Hz. Whilst the frequency was dropping to 49.2 Hz, or just after it reached that point, 40 MW of wind farms and more than 92 MW of other embedded generation (meaning, connected to the distribution system, rather than directly connected to the supergrid), such as landfill plant, tripped on the basis of the rate of change of frequency ('ROCOF') being high, just as it is supposed to do under the G 59/2 connection rules.

The frequency stabilised at 49.2 Hz for a short while. This would have been an acceptable frequency excursion, even though it was below the usual lower limit of 49.5 Hz, and recovery would not have been problematic. The fact that frequency stabilised at this level in spite of a beyond-design-basis event could be viewed as reassuring. Ireland, which is a smaller system and has a more temperamental (and therefore less stable) grid, sees about 10 frequency excursions below 49.5 Hz per year. (Its target frequency is 50 Hz, just as in Britain). Consumers would not have noticed the small drop in system frequency; other aspects of their supply, such as voltage, remained perfect. There would, therefore, have been no consumer detriment; all would have been well at this point, had nothing further untoward occurred.

However, further issues affecting smaller generators arose because the frequency remained below 49.5 Hz for more than a few seconds, and because some generators' control settings were wrong. The connection standard G 59/2 for embedded generation states that they must not trip (cease generating) as a result of sustained low frequency, until frequency has fallen below 47 Hz. However, a number of embedded generators used out-of-date control software that is not compliant with G59/2, as it erroneously trips them (as per the previous standard, G/59, in force when they were designed and specified) if frequency falls below 49.5 Hz for a few seconds. For this reason, another 279 MW of embedded generation tripped as a result of the low frequency whilst it was at 49.2 Hz. This was a problem as the Grid had no remaining available fast-acting generation, or demand-response, reserve margins. The frequency fell as a result to 48.792 Hz.

Grid rules state that as frequency falls below 48.8 Hz, distribution network operators must apply compulsory demand control. This should start, if time permits, with voltage reduction, rapidly followed by the compulsory disconnection of, in stages, up to a final total of 60 percent of all distribution-connected customers (a very small number of very large customers are connected directly to the supergrid; for them, other measures apply). There was no time to use voltage reduction (which keeps customers on supply, but subtly reduces their demand through reducing the voltage slightly); as a result, 546 MW of demand was automatically disconnected by distribution network operators. None of the directly supergrid-connected customers were cut off. National Grid had by now taken other measures to increase output at other generation sites (and demand had been reduced at those customer sites where the customer has volunteered for this to happen, in return for reimbursement, under demand-side response contracts with National Grid, or with their supplier). National Grid was then able to restore system frequency. The average duration of loss of supply to the 546 MW of mostly low-voltage-connected (e.g. domestic) demand affected was 20 minutes.

National Grid had time to issue a warning to all users of the supergrid – "demand control imminent" – which is one step away from its most serious warning "demand disconnection warning". During these incidents, the system was at risk to further generation loss which could have resulted in parts of the network being automatically disconnected by the operation of low frequency protection to ensure frequency is maintained within mandatory limits.[70][71][72]

August 2019

The third event occurred on 9 August 2019, when around a million customers across Great Britain found themselves without power.[73] Lightning struck a transmission line at 4:52 pm, causing the loss of 500 MW embedded (mostly solar) generation. Almost immediately, Little Barford Power Station and Hornsea Wind Farm tripped within seconds of each other, removing 1.378 GW of generation, which was in excess of the 1 GW of backup power (the size of the largest single expected loss) that the operator was maintaining at the time.[74] The grid frequency fell to 48.8 Hz before automatic load-shedding disconnected 5% of the local distribution networks (1.1 million customers) for 15 to 20 minutes; this action stabilised the remaining 95% of the system and prevented a larger blackout.[75][74]

Although power was maintained at all times to the railway network (but not to the signalling system), the reduction in frequency caused 60 Thameslink Class 700 and 717 trains to fail. Half were restarted by the drivers but the others required a technician to come out to the train to restart it.[74] This led to substantial travel disruption for several hours on the East Coast Main Line and Thameslink services. The supply to Newcastle Airport was also disrupted and a weakness was exposed in backup power arrangements at Ipswich Hospital.[74]

An investigation by Ofgem concluded in January 2020. It found that Little Barford and Hornsea One had failed to remain connected to the grid following the lightning strike, and their operators – RWE and Ørsted respectively – agreed to each pay £4.5 million to Ofgem's redress fund. Additionally, Ofgem fined distribution network operator UK Power Networks £1.5M for beginning to reconnect customers before being cleared to do so, although this breach of procedure did not affect the recovery of the system.[76][77]

Minor incidents

November 2015

On 4 November 2015 National Grid issued an emergency notice asking for voluntary power cuts because of "multiple plant breakdowns". No power cuts occurred but wholesale electricity prices rose dramatically, with the grid paying up to £2,500 per megawatt-hour.[78]

See also

References

  1. ^ a b "The GB electricity transmission network". Ofgem. Retrieved 25 June 2018.
  2. ^ "Nikola Tesla: Father of Our Modern Energy Systems". Just Energy. 30 March 2022. Retrieved 29 January 2023.
  3. ^ Massachusetts Institute of Technology. "NIKOLA TESLA". web.mit.edu. Retrieved 29 January 2023.
  4. ^ Alan Shaw (29 September 2005). (PDF). Royal Society of Edinburgh. Archived from the original (PDF) on 4 March 2009. Retrieved 12 November 2006.
  5. ^ "Survey of Belford 1995". North Northumberland Online.
  6. ^ . The National Trust. Archived from the original on 29 June 2011.
  7. ^ Electricity supply in the United Kingdom : a chronology – from the beginnings of the industry to 31 December 1985. The Electricity Council. 1987. ISBN 085188105X. OCLC 17343802.
  8. ^ The Secret Life of the National Grid: Wiring the Nation
  9. ^ a b c Gerard Gilbert (22 October 2010). "Power struggle: The National Grid was created to provide energy for all – but that's when the problems really began". The Independent. Archived from the original on 18 June 2022. Retrieved 21 August 2016.
  10. ^ Cochrane, Rob (1985). Power to the People. ISBN 0600358755.
  11. ^ (PDF). Archived from the original (PDF) on 22 March 2011. Retrieved 3 February 2011.
  12. ^ "Western Link". National Grid & Scottish Power. Retrieved 18 June 2019.
  13. ^ "National Grid builds UK's first T-pylon in East Huntspill as Hinkley work progresses". Burnham-On-Sea.com. 14 September 2021. Retrieved 16 September 2021.
  14. ^ "Electricity production by source". Our World in Data.
  15. ^ "International Energy Statistics – EIA". Eia.gov. Retrieved 21 August 2016.
  16. ^ (PDF). GOV.UK. Department of Energy & Climate Change. 31 March 2016. Archived from the original (PDF) on 3 July 2016 – via Internet Archive.
  17. ^ (PDF). GOV.UK. Department of Energy & Climate Change. 27 March 2014. Archived from the original (PDF) on 8 October 2016 – via Internet Archive.
  18. ^ "Energy Trends: UK electricity". GOV.UK.
  19. ^ "Historical electricity data". Retrieved 14 May 2016.
  20. ^ "Over the hills to Skye". Over the hills to Skye.
  21. ^ McCulloch, Scott (8 March 2016). "National Grid connection 'vital' for Scottish islands' renewables development". businessInsider.
  22. ^ "National Grid - SYS 2005 -". Archived from the original on 8 September 2012. Retrieved 9 January 2006.
  23. ^ Edwardes-Evans, Henry (11 May 2020). "UK electricity demand close to record low Sunday: National Grid". www.spglobal.com. from the original on 3 March 202.
  24. ^ [1][dead link]
  25. ^ "Zero-carbon explained". April 2020. Retrieved 11 February 2021.
  26. ^ Sarah Green (27 July 2020). "National Grid: UK's electricity system could go carbon-negative from 2033". edie.net. Retrieved 11 February 2021.
  27. ^ Rachel Morison (29 December 2020). "U.K. Power Grid Heads for Greenest Year as Renewables Grow". bloomberg. Retrieved 11 February 2021.
  28. ^ Reuters Staff (11 January 2021). "Britain sees greenest year for electricity in 2020 – National Grid". reuters. Retrieved 11 February 2021. {{cite web}}: |author= has generic name (help)
  29. ^ Katie Pavid (15 June 2020). "Britain goes two months without burning coal amid lockdown". Natural History Museum, London. Retrieved 11 February 2021.
  30. ^ Adam Lewis (8 December 2020). "Carbon in UK Power – Part 1: Lower Costs or Least Carbon?". Hartree Solutions. Retrieved 17 February 2021.
  31. ^ Adam Lewis (22 December 2020). "Carbon in UK Power – Part 2: Is It Time to Prioritise Carbon Over Price?". Hartree Solutions. Retrieved 17 February 2021.
  32. ^ Time to Take a Fresh Look at CHP... 27 February 2008 at the Wayback Machine, Simon Minett, director, DELTA Energy and Environment, October 2005
  33. ^ Metering Code of Practice 1 (Elexon Ltd)
  34. ^ Metering Code of Practice 2
  35. ^ Effect on Power Transfers 28 July 2012 at the Wayback Machine, 2009 Seven Year Statement, National Grid
  36. ^ "Western Link project". www.westernhvdclink.co.uk. Retrieved 10 February 2019.
  37. ^ PLC, National Grid Company. . National Grid – UK – Library. National Grid. Archived from the original on 19 December 2005. Retrieved 8 November 2013.
  38. ^ COM/2015/082 final: "Achieving the 10% electricity interconnection target" Text PDF page 2-5. European Commission, 25 February 2015. Mirror
  39. ^ "ElecLink: IGC approves start of tests at the converter stations". Getlink. 15 October 2020. Retrieved 9 September 2021.{{cite web}}: CS1 maint: url-status (link)
  40. ^ Stanford, Anna (21 September 2021). "Siemens Energy and Sumitomo Electric awarded EPC contract for Ireland-UK interconnector". Greenlink. Retrieved 23 September 2021.
  41. ^ . National Grid. 12 July 2016. Archived from the original on 21 July 2016. Retrieved 21 August 2016.
  42. ^ Grundy, Alice (25 September 2021). "Moroccan solar-plus-wind to be linked to GB in 'ground-breaking' Xlinks project". Current. Retrieved 29 September 2021.{{cite web}}: CS1 maint: url-status (link)
  43. ^ McCorkindale, Mollie (19 May 2021). "Top ten UK battery storage projects forecast for 2021 completion". Solar Power Portal. Retrieved 27 September 2021.
  44. ^ "Biggest storage battery in Europe built near Wiltshire village". BBC News. 15 July 2021. Retrieved 29 September 2021.
  45. ^ "About". Penso Power. 2021. Retrieved 27 September 2021.
  46. ^ a b (PDF), Operating the Electricity Transmission Networks in 2020 – Initial Consultation, National Grid, June 2009, archived from the original (PDF) on 23 December 2011, retrieved 8 January 2011
  47. ^ Gross, R; Heptonstall, P; Anderson, D; Green, T; Leach, M & Skea, J (March 2006). . UK Energy Research Centre. ISBN 1-903144-04-3. Archived from the original on 21 June 2008. Retrieved 15 July 2008.
  48. ^ . Archived from the original (PDF) on 14 July 2011. Retrieved 3 November 2010.
  49. ^ . Archived from the original (PDF) on 14 July 2011. Retrieved 3 November 2010.
  50. ^ "Wind Turbine Price List Uk". Archived from the original on 3 November 2010. Retrieved 3 November 2010.
  51. ^ "National Grid Control Centre Visit | Royal Meteorological Society". Rmets.org. 24 September 2012. Retrieved 21 August 2016.
  52. ^ "Power struggle: The National Grid was created to provide energy for all – but that's when the problems really began". The Independent. Archived from the original on 18 June 2022. Retrieved 21 August 2016.
  53. ^ Ward, Jillian. "U.K. Power Grid is Under Attack From Hackers Every Minute, Says Parliament" Bloomberg, 9 January 2015. Retrieved: 20 January 2015.
  54. ^ "Our Transmission Network". SPEnergyNetworks. Retrieved 24 January 2020.
  55. ^ "Transmission Network Use of System (TNUoS) Charges". National Grid ESO. Retrieved 8 December 2021.{{cite web}}: CS1 maint: url-status (link)
  56. ^ a b c Andrews, Dave. "What is the cost per kWh of bulk transmission / National Grid in the UK (note this excludes distribution costs) | Claverton Group". Claverton-energy.com. Retrieved 21 August 2016.
  57. ^ Inenco, 2015/16 Triads, published 31 March 2016
  58. ^ Trident Utilities, 2016/17 Triad Periods Confirmed, published 29 March 2017, accessed 3 April 2018
  59. ^ Stark, History repeats itself: trends are hard to change, published 26 March 2018, accessed 3 April 2018
  60. ^ Now Then Energy, Winter 20-21 TRIAD dates announced, published 29 March 2021, accessed 30 April 2021
  61. ^ Andrews, Dave. "Commercial Opportunities for Back-Up Generation and Load Reduction via National Grid, the National Electricity Transmission System Operator (NETSO) for England, Scotland, Wales and Offshore". Claverton-energy.com. Retrieved 21 August 2016.
  62. ^ "Grid Operations | Claverton Group". Claverton-energy.com. Retrieved 21 August 2016.
  63. ^ "National Grid ESO's newest frequency service Dynamic Regulation goes live". Current. 8 April 2022.
  64. ^ http://ireland2050.ie/questions/what-are-constraint-payments/ What are constraint payments? Energy Institute
  65. ^ . National Grid. Archived from the original on 11 January 2011. Retrieved 21 August 2016.
  66. ^ http://www.ofgem.gov.uk/NETWORKS/ELECDIST/QUALOFSERV/QOSINCENT/Documents1/200809%20Electricity%20Distribution%20Quality%20of%20Service%20report.doc.pdf[bare URL PDF]
  67. ^ . Ofgem.gov.uk. Archived from the original on 19 July 2012. Retrieved 21 August 2016.
  68. ^ "Power cut causes chaos". BBC News. 28 August 2003.
  69. ^ a b "Report on support investigations into recent blackouts in London and West Midlands" (PDF). Ofgem. 25 June 2004. Retrieved 28 November 2022.
  70. ^ Murad Ahmed, Steve Hawkes (28 May 2008). "Blackouts hit thousands as generators fail". The Times.{{cite news}}: CS1 maint: uses authors parameter (link)
  71. ^ Mark Milner, Graeme Wearden (28 May 2008). "Q&A: Blackout Britain". The Guardian.{{cite news}}: CS1 maint: uses authors parameter (link)
  72. ^ George South (28 May 2008). "iPM: Blackout Britain?". BBC. Retrieved 21 August 2016.
  73. ^ "Major power failure affects homes and transport". BBC. 9 August 2019. Retrieved 9 August 2019.
  74. ^ a b c d https://www.nationalgrideso.com/document/151081/download Interim Report into the Low Frequency Demand Disconnection (LFDD) following Generator Trips and Frequency Excursion on 9 Aug 2019 - 16 August 2019
  75. ^ @enappsys (9 August 2019). "GB : Frequency drops off the chart to..." (Tweet) – via Twitter.
  76. ^ Stoker, Liam (3 January 2020). "Blackout investigation: Power firms fined as Ofgem 'accelerates' ESO review". Current News. Retrieved 8 January 2020.
  77. ^ "Companies pay £10.5 million over 9 August power cut". Ofgem. 3 January 2020.
  78. ^ Stacey, Kiran; Adams, Christopher (5 November 2015). "National Grid in emergency plea for heavy users to power down". Financial Times. pp. front page.

Further reading

External links

  • , National Grid's Seven Year Statement (2008)
  • The Statement of the Use of System Charging Methodology[permanent dead link], National Grid
  • , National Grid
  • National Grid live data, ELEXON
  • UK National Grid Status
  • , Scott Butler
  • , UK Competition Commission Report 1987
  • Map of GB power stations and national grid, BBC website, but map revised by Deloitte & Touche, 2003.
  • Carbon-intensity variations in the GB grid

national, grid, great, britain, this, article, about, power, grid, great, britain, ordnance, survey, national, grid, mapping, ordinates, great, britain, ordnance, survey, national, grid, company, national, grid, electricity, sector, united, kingdom, national, . This article is about the power grid in Great Britain For the UK Ordnance Survey National Grid for mapping co ordinates in Great Britain see Ordnance Survey National Grid For the company see National Grid plc In the electricity sector in the United Kingdom the National Grid is the high voltage electric power transmission network serving Great Britain connecting power stations and major substations and ensuring that electricity generated anywhere on it can be used to satisfy demand elsewhere The network covers the great majority of Great Britain and several of the surrounding islands It does not cover Northern Ireland which is part of a single electricity market with the Republic of Ireland 400 kV power line in Cheshire The GB grid is connected as a wide area synchronous grid nominally running at 50 hertz There are also undersea interconnections to other grids in the Isle of Man Northern Ireland the Republic of Ireland France Belgium the Netherlands and Norway On the breakup of the Central Electricity Generating Board in 1990 the ownership and operation of the National Grid in England and Wales passed to National Grid Company plc later to become National Grid Transco and now National Grid plc In Scotland the grid was already split into two separate entities one for southern and central Scotland and the other for northern Scotland with interconnectors The first is owned and maintained by SP Energy Networks a subsidiary of Scottish Power and the other by SSE However National Grid plc continues to be the transmission system operator for the whole GB grid 1 Contents 1 History 2 Characteristics of the grid 2 1 Network size 2 2 Decarbonisation 2 3 Losses 2 4 Power flow 2 5 Interconnectors 2 6 Grid storage 3 Reserve services and frequency response 4 Control of the grid 5 Transmission costs 5 1 Triad demand 5 2 Estimating costs per kW h of transmission 5 3 Generation charges 5 4 Demand charges 5 5 Constraint payments 6 Major incidents 6 1 August 2003 6 2 May 2008 6 3 August 2019 7 Minor incidents 7 1 November 2015 8 See also 9 References 10 Further reading 11 External linksHistory EditThis section needs additional citations for verification Please help improve this article by adding citations to reliable sources Unsourced material may be challenged and removed February 2019 Learn how and when to remove this template message Electricity pylons in a suburban area of Pudsey West Yorkshire At the end of the 19th century Nikola Tesla established the principles of three phase high voltage electric power distribution while he was working for Westinghouse in the United States 2 3 The first use of this system in the United Kingdom was by Charles Merz of the Merz amp McLellan consulting partnership at his Neptune Bank Power Station near Newcastle upon Tyne This opened in 1901 4 and by 1912 had developed into the largest integrated power system in Europe 5 The rest of the country however continued to use a patchwork of small supply networks In 1925 the British government asked Lord Weir a Glaswegian industrialist to solve the problem of Britain s inefficient and fragmented electricity supply industry Weir consulted Merz and the result was the Electricity Supply Act 1926 which recommended that a national gridiron supply system be created 6 The 1926 Act created the Central Electricity Board which set up the UK s first synchronised nationwide AC grid running at 132 kV 50 Hz National Grid helicopter inspecting overhead cables in Greater Manchester The grid was created with 6 400 kilometres 4 000 mi of cables mostly overhead linking the 122 most efficient power stations The first grid tower was erected near Edinburgh on 14 July 1928 7 and work was completed in September 1933 ahead of schedule and on budget 8 9 It began operating in 1933 as a series of regional grids with auxiliary interconnections for emergency use Following the unauthorised but successful short term parallelling of all regional grids by the night time engineers on 29 October 1937 10 by 1938 the grid was operating as a national system The growth by then in the number of electricity users was the fastest in the world rising from three quarters of a million in 1920 to nine million in 1938 9 The grid proved its worth during the Blitz when South Wales provided power to replace lost output from Battersea and Fulham power stations 9 The grid was nationalised by the Electricity Act 1947 which also created the British Electricity Authority In 1949 the British Electricity Authority decided to upgrade the grid by adding 275 kV links At its inception in 1950 the 275 kV Transmission System was designed to form part of a national supply system with an anticipated total demand of 30 000 MW by 1970 The predicted demand was already exceeded by 1960 This rapid growth led the Central Electricity Generating Board created in 1958 to carry out a study in 1960 of future transmission needs The report was completed in September 1960 and its study is described in a paper presented to the Institution of Electrical Engineers by E S Booth D Clark J L Egginton and J S Forrest in 1962 Considered in the study together with the increased demand was the effect on the transmission system of the rapid advances in generator design resulting in projected power stations of 2 000 3 000 MW installed capacity These new stations were mostly to be sited where advantage could be taken of a surplus of cheap low grade fuel and adequate supplies of cooling water but these sites did not coincide with the load centres West Burton s 4 500 MW machines in the Nottinghamshire coalfield near the River Trent is an example These developments shifted the emphasis on the transmission system from interconnection to bulk power transfers from the generation areas to the load centres such as the anticipated transfer in 1970 of some 6 000 MW from the Midlands to the home counties Continued reinforcement and extension of the 275 kV systems was examined as a possible solution However in addition to the technical problem of high fault levels many more lines would have been required to obtain the estimated transfers at 275 kV As this was not consistent with the Central Electricity Generating Board s policy of preservation of amenities a better solution was sought Consideration was given to 400 kV and 500 kV schemes both gave a sufficient margin for future expansion The decision in favour of a 400 kV system was made for two main reasons Firstly the majority of the 275 kV lines could be uprated to 400 kV and secondly it was envisaged that operation at 400 kV could begin in 1965 compared with 1968 for a 500 kV scheme Design work was started and in order to meet the programme for 1965 it was necessary for the contract engineering for the first projects to run concurrently with the design One of these projects was the West Burton 400 kV Indoor Substation the first section of which was commissioned in June 1965 From 1965 the grid was partly upgraded to 400 kV beginning with a 150 mile 240 km line from Sundon to West Burton to become the Supergrid In the 2010 issue of the code that governs the National Grid the Grid Code 11 the Supergrid is defined as those parts of the British electricity transmission system that are connected at voltages in excess of 200 kV The 2 2 GW undersea Western HVDC Link from Scotland to North Wales was built in 2013 2018 12 This was the first major non alternating current grid link within Great Britain although interconnectors to foreign grids already used HVDC In 2021 a new non lattice design of electricity pylon the T pylon was built near East Huntspill Somerset for the new 35 mile Hinkley Point C to Avonmouth connection 13 Characteristics of the grid Edit UK electricity production by source 1985 2020 14 15 16 17 18 Electricity supplied net 1920 2014 19 External images Current grid status charts Current grid status dialsThe contiguous synchronous grid covers England including the Isle of Wight Scotland including some of the Scottish islands such as Orkney Skye 20 and the Western Isles which have limited connectivity 21 Wales and the Isle of Man Network size Edit The following figures are taken from the 2005 Seven Year Statement 22 Maximum demand 2005 6 63 GW approx 81 39 of capacity Minimum demand 2020 May 15 3 GW 23 Annual electrical energy used in the UK is around 360 TWh 1 3 EJ Capacity 2005 6 79 9 GW or 80 GW per the 2008 Seven Year Statement 24 Number of large power stations connected to it 181 Length of 400 kV grid 11 500 km circuit Length of 275 kV grid 9 800 km circuit Length of 132 kV or lower grid 5 250 km circuit Total generating capacity is supplied roughly equally by renewable gas fired nuclear coal fired power stations Annual energy transmitted in the UK grid is around 300 360 TWh 1 1 1 3 EJ with an average load factor of 72 i e 3 6 1011 8 760 57 106 needs update Decarbonisation Edit The national grid has a stretch target to be carbon neutral or negative by 2033 well ahead of the UK s national target to achieve this by 2050 It also aims to have the capability to be zero carbon as early as 2025 meaning that if energy suppliers are able to produce sufficient green power the grid could theoretically run without any greenhouse gas emissions at all i e no carbon capture or offsetting would be needed as is the case with net zero 25 In 2020 about 40 of the grid s energy came from burning natural gas and it is not expected that anywhere close to sufficient green power will be available to run the grid on zero carbon in 2025 except perhaps on the very windiest days Analysts such as Hartree Solutions considered in 2020 that getting to net zero by 2050 would be challenging even more so to reach net zero by 2033 There has however been sustained progress towards carbon neutrality with carbon intensity falling by 53 in the five years to 2020 The phase out of coal is progressing rapidly with only 1 6 of the UK s electricity coming from coal in 2020 compared with about 25 in 2015 2020 saw the UK go more than two months without needing to burn any coal for electricity the longest period since the industrial revolution 26 27 28 29 30 31 Losses Edit Figures are again from the 2005 Seven Year Statement Joule heating in cables 857 8 MW Fixed losses 266 MW consists of corona and iron loss can be 100 MW higher in adverse weather Substation transformer heating losses 142 4 MW Generator transformer heating losses 157 3 MW Total losses 1 423 5 MW 2 29 of peak demand Although overall losses in the national grid are low there are significant further losses in onward electricity distribution to the consumer causing a total distribution loss of about 7 7 citation needed Losses differ significantly for customers connected at different voltages connected at high voltage the total losses are about 2 6 at medium voltage 6 4 and at low voltage 12 2 32 Generated power entering the grid is metered at the high voltage side of the generator transformer 33 34 Any power losses in the generator transformer are therefore accounted to the generating company not to the grid system The power loss in the generator transformer does not contribute to the grid losses Power flow Edit In 2009 10 there was an average power flow of about 11 GW from the north of the UK particularly from Scotland and northern England to the south of the UK across the grid This flow was anticipated to grow to about 12 GW by 2014 35 Completion of the Western HVDC Link in 2018 added capacity for a flow of 2 2 GW between Western Scotland and North Wales 36 Because of the power loss associated with this north to south flow the effectiveness and efficiency of new generation capacity is significantly affected by its location For example new generating capacity on the south coast has about 12 greater effectiveness due to reduced transmission system power losses compared to new generating capacity in north England and about 20 greater effectiveness than in northern Scotland 37 Interconnectors Edit Existing links Under construction Proposed Some of these HVDC lines transfer power from renewable sources such as hydro and wind For names see also the annotated version needs update There is a 40 MW AC cable to the Isle of Man the Isle of Man to England Interconnector The UK grid is connected to adjacent European electrical grids by submarine power cables at an electricity interconnection level transmission capacity relative to production capacity which was 6 as of 2014 update 38 As of 2022 the total capacity of these connectors is about 7 7 GW citation needed They include direct current cables to northern France 2 GW HVDC Cross Channel 1 GW HVDC IFA 2 1 GW ElecLink via the Channel Tunnel 39 Belgium 1 GW HVDC Nemo Link the Netherlands 1 GW HVDC BritNed Norway 1 4 GW HDVC North Sea Link Northern Ireland 500 MW HVDC Moyle Interconnector and the Republic of Ireland 500 MW HVDC East West Interconnector A link is under construction to Denmark 1 4 GW Viking Link which is due to be completed in 2023 A further 500 MW link with the Republic of Ireland Greenlink is scheduled for 2024 40 Further potential schemes include links with Germany NeuConnect 1 4 GW Iceland Icelink around 1 GW 41 and Morocco 3 6 GW from new battery backed solar generation 42 Grid storage Edit The UK grid has access to large pumped storage systems notably Dinorwig Power Station which can provide 1 7 GW for 5 6 hours and the smaller Cruachan and Ffestiniog There are also some grid batteries As of May 2021 1 3 GW of battery storage was operating in the United Kingdom with 16 GW of projects in the pipeline potentially deployable over the next few years 43 A 100 MW power Chinese financed plant at Minety Wiltshire was reported to be the largest in Europe when it opened in July 2021 44 when a 50 MW extension is completed the site s storage capacity will be 266 MWh 45 Reserve services and frequency response EditMain article National Grid Reserve Service National Grid is responsible for contracting short term generating provision to cover demand prediction errors and sudden failures at power stations This covers a few hours of operation giving time for market contracts to be established to cover longer term balancing Frequency response reserves act to keep the system s AC frequency within 1 of 50 Hz except in exceptional circumstances These are used on a second by second basis to either lower the demand or to provide extra generation 46 Reserve services are a group of services each acting within different response times 46 Fast Reserve rapid delivery within two minutes of increased generation or reduced demand sustainable for a minimum of 15 minutes Fast Start generation units that start from a standstill and deliver power within five minutes automatically or within seven minutes of a manual instruction with generation maintained for a minimum of four hours Demand Management reduction in demand of at least 25 MW from large power users for at least an hour Short Term Operating Reserve STOR generation of at least 3 MW from a single or aggregation of sites within four hours of instruction and maintained for at least two hours BM Start Up mainstream major generation units maintained in either an energy readiness or hot standby state These reserves are sized according to three factors 47 The largest credible single generation failure event which is currently either Sizewell B nuclear power station 1 260 MW or one cable of the HVDC Cross Channel interconnector 1 000 MW The general anticipated availability of all generation plants Anticipated demand prediction errorsControl of the grid EditThe English and Welsh parts of the National Grid are controlled from the National Grid Control Centre which is located in St Catherine s Lodge Sindlesham Wokingham in Berkshire 48 49 50 51 It is sometimes described as being a secret location 52 As of 2015 update the system is under consistent cyber attack 53 Although the transmission network in Scotland is owned by separate companies SP Transmission plc part of Scottish Power in the south and Scottish Hydro Electric Transmission plc part of Scottish and Southern Electricity Networks in the north 54 overall control rests with National Grid Electricity System Operator 1 Transmission costs EditThe costs of operating the National Grid System are recouped by National Grid Electricity System Operator NGESO through levying of Transmission Network Use of System TNUoS charges on the users of the system 55 The costs are split between the generators and the users of electricity 56 Tariffs are set annually by NGESO and the country is divided into zones each with a different tariff for generation and consumption In general tariffs are higher for generators in the north and consumers in the south since there is generally a north south flow of electricity Triad demand Edit Triad demand is a metric of demand which reports retrospectively three numbers about peak demand between November and February inclusive each winter In order to encourage usage of the National Grid to be less peaky the triad is used as the basis for extra charges paid by the users the licensed electricity suppliers to the National Grid the users pay less if they can manage their usage so as to be less peaky For each year s calculation historic system demand metrics are analysed to determine three half hour periods of high average demand the three periods are known as triads The periods are a the period of peak system demand and b two other periods of highest demand which are separated from peak system demand and from each other by at least ten days For power stations the chargeable demand is only the net site demand per CUSC rule 14 17 10 so when the site is net exporting i e total metered generation at that site exceeds total separately metered station demand that separately metered station demand shall not be liable for demand TNUoS charges in relation to the station demand at triad Triad dates in recent years were Year Triad 1 Triad 2 Triad 32015 16 57 Wednesday 25 November 2015 17 00 17 30 Tuesday 19 January 2016 17 00 17 30 Monday 15 February 2016 18 00 18 302016 17 58 Monday 5 December 2016 17 00 17 30 Thursday 5 January 2017 17 00 17 30 Monday 23 January 2017 17 00 17 302017 18 59 Monday 11 December 2017 17 30 18 00 Monday 26 February 2018 18 30 19 00 Monday 5 February 2018 18 00 18 302018 192019 202020 21 60 Monday 7 December 2020 17 00 17 30 Thursday 7 January 2021 17 30 18 00 Wednesday 10 February 2021 18 00 18 30In April of each year each licensed electricity supplier such as Centrica BGB etc is charged a yearly fee for the load it imposed on the grid during those three half hours of the previous winter Exact charges vary depending on the distance from the centre of the network but in the South West it is 21 000 MW citation needed The average for the whole country is about 15 000 MW This is a means for National Grid to recover some of its costs and to impose an incentive on users to minimise consumption at peak thereby easing the need for investment in the system It is estimated that these charges reduced peak load by about 1 GW out of say 57 GW citation needed This is the main source of income which National Grid uses to cover its costs for high voltage long distance transmission lower voltage distribution is charged separately The grid also charges an annual fee to cover the cost of generators distribution networks and large industrial users connecting Triad charges encourage users to cut load at peak periods this is often achieved by using diesel generators Such generators are also routinely used by National Grid 61 Estimating costs per kW h of transmission Edit If the total TNUoS or Triad receipts say 15 000 MW year 50 000 MW 750 million year is divided by the total number of units delivered by the UK generating system in a year the total number of units sold say 360 terawatt hours 1 3 EJ 56 then a crude estimate can be made of transmission costs and one gets the figure of around 0 2p kW h Other estimates also give a figure of 0 2p kW h 56 However Bernard Quigg notes According to the 06 07 annual accounts for NGC UK transmission NGC carried 350TW h for an income of 2012m in 2007 i e NGC receives 0 66p per kW hour With two years inflation to 2008 9 say 0 71p per kW h 62 but this also includes generators connection fees Generation charges Edit In order to be allowed to supply electricity to the transmission system generators must be licensed by BEIS and enter into a connection agreement with NGET which also grants Transmission Entry Capacity TEC Generators contribute to the costs of running the system by paying for TEC at the generation TNUoS tariffs set by NGET This is charged on a maximum capacity basis In other words a generator with 100 MW of TEC who only generated at a maximum rate of 75 MW during the year would still be charged for the full 100 MW of TEC citation needed In some cases there are negative TNUoS tariffs These generators are paid an amount based on their peak net supply over three proving runs over the course of the year This represents the reduction in costs caused by having a generator close to the centre of demand of the country citation needed National Grid uses a grid services market Dynamic Containment started in October 2020 initially priced at 17 per MW per hour and Dynamic Regulation DR started in April 2022 63 Demand charges Edit This section does not cite any sources Please help improve this section by adding citations to reliable sources Unsourced material may be challenged and removed November 2014 Learn how and when to remove this template message Consumers of electricity are split into two categories half hourly metered HH and non half hourly metered NHH Customers whose peak demand is sufficiently high are obliged to have a HH meter which in effect takes a meter reading every 30 minutes The rates at which charges are levied on these customers electricity suppliers therefore varies 17 520 times a non leap year The TNUoS charges for a HH metered customer are based on their demand during three half hour periods of greatest demand between November and February known as the Triad Due to the nature of electricity demand in the UK the three Triad periods always fall in the early evening and must be separated by at least ten clear working days The TNUoS charges for a HH customer are simply their average demand during the triad periods multiplied by the tariff for their zone Therefore as of 2007 update a customer in London with a 1 MW average demand during the three triad periods would pay 19 430 in TNUoS charges TNUoS charges levied on NHH metered customers are much simpler A supplier is charged for the sum of their total consumption between 16 00 and 19 00 every day over a year multiplied by the relevant tariff Constraint payments Edit Constraint payments are payments to generators above a certain size where the National Grid gives them dispatch instructions that they are unable to take the electricity that the generators would normally provide This can be due to a lack of transmission capacity a shortfall in demand or unexpected excess generation A constraint payment is recompense for the reduction in generation 64 Major incidents EditPower cuts because of problems with the infrastructure of the Supergrid or lack of generation to supply it with sufficient power are very rare The nominal standard of security of supply is for power cuts due to lack of generation to occur in nine winters in a hundred The overall performance measure for electricity transmission is published on NGET s website 65 and includes a simple high level figure on transmission availability and reliability of supply For 2008 9 this was 99 99979 Issues affecting the low voltage distribution systems for which National Grid is not responsible cause almost all the 60 minutes or so per year on average of domestic power cuts Most of these low voltage distribution interruptions are in turn the fault of third parties such as workmen drilling through the street mains or subterranean higher voltage cables this does not happen to major transmission lines which are for the most part overhead on pylons For comparison with Supergrid availability Ofgem the electricity regulator has published figures on the performance of 14 electricity distributors 66 67 Since 1990 there have been three power cuts of high national prominence that were linked to National Grid two due to generation issues August 2003 Edit See also 2003 London Blackout The first case was in August 2003 and related to the condition of National Grid s assets In the early evening of 28 August a power cut affected 476 000 customers in South London as well as the London Underground and some rail services Some news reports accused National Grid of under investment in new assets at the time A transformer oil leak had been left untreated except for top ups for many months pending a proper fix It also transpired that there was a significant error in a protection relay setting which became evident resulting in a power cut only when the first fault the oil leak had a real effect National Grid took some time to admit to these aspects of the incident 68 69 A second event happened on 5 September 2003 which affected 220 000 customers in East Birmingham This was attributed to an error made by National Grid when commissioning protection systems 69 May 2008 Edit The second case was in May 2008 and related to generation issues for which National Grid was not responsible A power cut took place in which a protective shutdown of parts of the network was undertaken by the distribution network operators under pre arranged rules due to a sudden loss of generating capacity causing a severe drop in system frequency First two of Britain s largest power stations Longannet in Fife and Sizewell B in Suffolk shut down unexpectedly tripped within five minutes of one another There was no relationship between the two trips the first did not cause the second Such a loss is most unusual at that time Grid secured only against the loss of 1320 MW the infrequent infeed loss limit which rose to 1800 MW from 2014 The two shutdowns caused a sudden 1 510 MW adverse change in the balance of generation and demand on the Supergrid and the frequency dropped to 49 2 Hz Whilst the frequency was dropping to 49 2 Hz or just after it reached that point 40 MW of wind farms and more than 92 MW of other embedded generation meaning connected to the distribution system rather than directly connected to the supergrid such as landfill plant tripped on the basis of the rate of change of frequency ROCOF being high just as it is supposed to do under the G 59 2 connection rules The frequency stabilised at 49 2 Hz for a short while This would have been an acceptable frequency excursion even though it was below the usual lower limit of 49 5 Hz and recovery would not have been problematic The fact that frequency stabilised at this level in spite of a beyond design basis event could be viewed as reassuring Ireland which is a smaller system and has a more temperamental and therefore less stable grid sees about 10 frequency excursions below 49 5 Hz per year Its target frequency is 50 Hz just as in Britain Consumers would not have noticed the small drop in system frequency other aspects of their supply such as voltage remained perfect There would therefore have been no consumer detriment all would have been well at this point had nothing further untoward occurred However further issues affecting smaller generators arose because the frequency remained below 49 5 Hz for more than a few seconds and because some generators control settings were wrong The connection standard G 59 2 for embedded generation states that they must not trip cease generating as a result of sustained low frequency until frequency has fallen below 47 Hz However a number of embedded generators used out of date control software that is not compliant with G59 2 as it erroneously trips them as per the previous standard G 59 in force when they were designed and specified if frequency falls below 49 5 Hz for a few seconds For this reason another 279 MW of embedded generation tripped as a result of the low frequency whilst it was at 49 2 Hz This was a problem as the Grid had no remaining available fast acting generation or demand response reserve margins The frequency fell as a result to 48 792 Hz Grid rules state that as frequency falls below 48 8 Hz distribution network operators must apply compulsory demand control This should start if time permits with voltage reduction rapidly followed by the compulsory disconnection of in stages up to a final total of 60 percent of all distribution connected customers a very small number of very large customers are connected directly to the supergrid for them other measures apply There was no time to use voltage reduction which keeps customers on supply but subtly reduces their demand through reducing the voltage slightly as a result 546 MW of demand was automatically disconnected by distribution network operators None of the directly supergrid connected customers were cut off National Grid had by now taken other measures to increase output at other generation sites and demand had been reduced at those customer sites where the customer has volunteered for this to happen in return for reimbursement under demand side response contracts with National Grid or with their supplier National Grid was then able to restore system frequency The average duration of loss of supply to the 546 MW of mostly low voltage connected e g domestic demand affected was 20 minutes National Grid had time to issue a warning to all users of the supergrid demand control imminent which is one step away from its most serious warning demand disconnection warning During these incidents the system was at risk to further generation loss which could have resulted in parts of the network being automatically disconnected by the operation of low frequency protection to ensure frequency is maintained within mandatory limits 70 71 72 August 2019 Edit The third event occurred on 9 August 2019 when around a million customers across Great Britain found themselves without power 73 Lightning struck a transmission line at 4 52 pm causing the loss of 500 MW embedded mostly solar generation Almost immediately Little Barford Power Station and Hornsea Wind Farm tripped within seconds of each other removing 1 378 GW of generation which was in excess of the 1 GW of backup power the size of the largest single expected loss that the operator was maintaining at the time 74 The grid frequency fell to 48 8 Hz before automatic load shedding disconnected 5 of the local distribution networks 1 1 million customers for 15 to 20 minutes this action stabilised the remaining 95 of the system and prevented a larger blackout 75 74 Although power was maintained at all times to the railway network but not to the signalling system the reduction in frequency caused 60 Thameslink Class 700 and 717 trains to fail Half were restarted by the drivers but the others required a technician to come out to the train to restart it 74 This led to substantial travel disruption for several hours on the East Coast Main Line and Thameslink services The supply to Newcastle Airport was also disrupted and a weakness was exposed in backup power arrangements at Ipswich Hospital 74 An investigation by Ofgem concluded in January 2020 It found that Little Barford and Hornsea One had failed to remain connected to the grid following the lightning strike and their operators RWE and Orsted respectively agreed to each pay 4 5 million to Ofgem s redress fund Additionally Ofgem fined distribution network operator UK Power Networks 1 5M for beginning to reconnect customers before being cleared to do so although this breach of procedure did not affect the recovery of the system 76 77 Minor incidents EditNovember 2015 Edit On 4 November 2015 National Grid issued an emergency notice asking for voluntary power cuts because of multiple plant breakdowns No power cuts occurred but wholesale electricity prices rose dramatically with the grid paying up to 2 500 per megawatt hour 78 See also EditDemand response Cost of electricity by source Economics of nuclear power plants for cost comparisons Energy security and renewable technology Intermittent energy source TV pickup 2007 switching station flood at Walham Gloucestershire List of energy storage projects List of major power outages Spark spread calculating the cost of back up Load management Three phase electric power List of HVDC projects List of high voltage underground and submarine cables National Grid Reserve Service Energy in the United Kingdom High voltage substations in the United KingdomReferences Edit a b The GB electricity transmission network Ofgem Retrieved 25 June 2018 Nikola Tesla Father of Our Modern Energy Systems Just Energy 30 March 2022 Retrieved 29 January 2023 Massachusetts Institute of Technology NIKOLA TESLA web mit edu Retrieved 29 January 2023 Alan Shaw 29 September 2005 Kelvin to Weir and on to GB SYS 2005 PDF Royal Society of Edinburgh Archived from the original PDF on 4 March 2009 Retrieved 12 November 2006 Survey of Belford 1995 North Northumberland Online Lighting by electricity The National Trust Archived from the original on 29 June 2011 Electricity supply in the United Kingdom a chronology from the beginnings of the industry to 31 December 1985 The Electricity Council 1987 ISBN 085188105X OCLC 17343802 The Secret Life of the National Grid Wiring the Nation a b c Gerard Gilbert 22 October 2010 Power struggle The National Grid was created to provide energy for all but that s when the problems really began The Independent Archived from the original on 18 June 2022 Retrieved 21 August 2016 Cochrane Rob 1985 Power to the People ISBN 0600358755 the British Grid Code PDF Archived from the original PDF on 22 March 2011 Retrieved 3 February 2011 Western Link National Grid amp Scottish Power Retrieved 18 June 2019 National Grid builds UK s first T pylon in East Huntspill as Hinkley work progresses Burnham On Sea com 14 September 2021 Retrieved 16 September 2021 Electricity production by source Our World in Data International Energy Statistics EIA Eia gov Retrieved 21 August 2016 UK Energy Statistics 2015 amp Q4 2015 PDF GOV UK Department of Energy amp Climate Change 31 March 2016 Archived from the original PDF on 3 July 2016 via Internet Archive UK Energy Statistics PDF GOV UK Department of Energy amp Climate Change 27 March 2014 Archived from the original PDF on 8 October 2016 via Internet Archive Energy Trends UK electricity GOV UK Historical electricity data Retrieved 14 May 2016 Over the hills to Skye Over the hills to Skye McCulloch Scott 8 March 2016 National Grid connection vital for Scottish islands renewables development businessInsider National Grid SYS 2005 Archived from the original on 8 September 2012 Retrieved 9 January 2006 Edwardes Evans Henry 11 May 2020 UK electricity demand close to record low Sunday National Grid www spglobal com Archived from the original on 3 March 202 1 dead link Zero carbon explained April 2020 Retrieved 11 February 2021 Sarah Green 27 July 2020 National Grid UK s electricity system could go carbon negative from 2033 edie net Retrieved 11 February 2021 Rachel Morison 29 December 2020 U K Power Grid Heads for Greenest Year as Renewables Grow bloomberg Retrieved 11 February 2021 Reuters Staff 11 January 2021 Britain sees greenest year for electricity in 2020 National Grid reuters Retrieved 11 February 2021 a href Template Cite web html title Template Cite web cite web a author has generic name help Katie Pavid 15 June 2020 Britain goes two months without burning coal amid lockdown Natural History Museum London Retrieved 11 February 2021 Adam Lewis 8 December 2020 Carbon in UK Power Part 1 Lower Costs or Least Carbon Hartree Solutions Retrieved 17 February 2021 Adam Lewis 22 December 2020 Carbon in UK Power Part 2 Is It Time to Prioritise Carbon Over Price Hartree Solutions Retrieved 17 February 2021 Time to Take a Fresh Look at CHP Archived 27 February 2008 at the Wayback Machine Simon Minett director DELTA Energy and Environment October 2005 Metering Code of Practice 1 Elexon Ltd Metering Code of Practice 2 Effect on Power Transfers Archived 28 July 2012 at the Wayback Machine 2009 Seven Year Statement National Grid Western Link project www westernhvdclink co uk Retrieved 10 February 2019 PLC National Grid Company 2002 Seven Year Statement National Grid UK Library National Grid Archived from the original on 19 December 2005 Retrieved 8 November 2013 COM 2015 082 final Achieving the 10 electricity interconnection target Text PDF page 2 5 European Commission 25 February 2015 Archive Mirror ElecLink IGC approves start of tests at the converter stations Getlink 15 October 2020 Retrieved 9 September 2021 a href Template Cite web html title Template Cite web cite web a CS1 maint url status link Stanford Anna 21 September 2021 Siemens Energy and Sumitomo Electric awarded EPC contract for Ireland UK interconnector Greenlink Retrieved 23 September 2021 Interconnectors Iceland National Grid 12 July 2016 Archived from the original on 21 July 2016 Retrieved 21 August 2016 Grundy Alice 25 September 2021 Moroccan solar plus wind to be linked to GB in ground breaking Xlinks project Current Retrieved 29 September 2021 a href Template Cite web html title Template Cite web cite web a CS1 maint url status link McCorkindale Mollie 19 May 2021 Top ten UK battery storage projects forecast for 2021 completion Solar Power Portal Retrieved 27 September 2021 Biggest storage battery in Europe built near Wiltshire village BBC News 15 July 2021 Retrieved 29 September 2021 About Penso Power 2021 Retrieved 27 September 2021 a b Appendix D Description of Balancing Services PDF Operating the Electricity Transmission Networks in 2020 Initial Consultation National Grid June 2009 archived from the original PDF on 23 December 2011 retrieved 8 January 2011 Gross R Heptonstall P Anderson D Green T Leach M amp Skea J March 2006 The Costs and Impacts of Intermittency UK Energy Research Centre ISBN 1 903144 04 3 Archived from the original on 21 June 2008 Retrieved 15 July 2008 Agenda 22 May 2007 Archived from the original PDF on 14 July 2011 Retrieved 3 November 2010 NETA Despatch Instruction Guide Archived from the original PDF on 14 July 2011 Retrieved 3 November 2010 Wind Turbine Price List Uk Archived from the original on 3 November 2010 Retrieved 3 November 2010 National Grid Control Centre Visit Royal Meteorological Society Rmets org 24 September 2012 Retrieved 21 August 2016 Power struggle The National Grid was created to provide energy for all but that s when the problems really began The Independent Archived from the original on 18 June 2022 Retrieved 21 August 2016 Ward Jillian U K Power Grid is Under Attack From Hackers Every Minute Says Parliament Bloomberg 9 January 2015 Retrieved 20 January 2015 Our Transmission Network SPEnergyNetworks Retrieved 24 January 2020 Transmission Network Use of System TNUoS Charges National Grid ESO Retrieved 8 December 2021 a href Template Cite web html title Template Cite web cite web a CS1 maint url status link a b c Andrews Dave What is the cost per kWh of bulk transmission National Grid in the UK note this excludes distribution costs Claverton Group Claverton energy com Retrieved 21 August 2016 Inenco 2015 16 Triads published 31 March 2016 Trident Utilities 2016 17 Triad Periods Confirmed published 29 March 2017 accessed 3 April 2018 Stark History repeats itself trends are hard to change published 26 March 2018 accessed 3 April 2018 Now Then Energy Winter 20 21 TRIAD dates announced published 29 March 2021 accessed 30 April 2021 Andrews Dave Commercial Opportunities for Back Up Generation and Load Reduction via National Grid the National Electricity Transmission System Operator NETSO for England Scotland Wales and Offshore Claverton energy com Retrieved 21 August 2016 Grid Operations Claverton Group Claverton energy com Retrieved 21 August 2016 National Grid ESO s newest frequency service Dynamic Regulation goes live Current 8 April 2022 http ireland2050 ie questions what are constraint payments What are constraint payments Energy Institute Transmission Performance Report National Grid Archived from the original on 11 January 2011 Retrieved 21 August 2016 http www ofgem gov uk NETWORKS ELECDIST QUALOFSERV QOSINCENT Documents1 200809 20Electricity 20Distribution 20Quality 20of 20Service 20report doc pdf bare URL PDF Information for Consumers Ofgem gov uk Archived from the original on 19 July 2012 Retrieved 21 August 2016 Power cut causes chaos BBC News 28 August 2003 a b Report on support investigations into recent blackouts in London and West Midlands PDF Ofgem 25 June 2004 Retrieved 28 November 2022 Murad Ahmed Steve Hawkes 28 May 2008 Blackouts hit thousands as generators fail The Times a href Template Cite news html title Template Cite news cite news a CS1 maint uses authors parameter link Mark Milner Graeme Wearden 28 May 2008 Q amp A Blackout Britain The Guardian a href Template Cite news html title Template Cite news cite news a CS1 maint uses authors parameter link George South 28 May 2008 iPM Blackout Britain BBC Retrieved 21 August 2016 Major power failure affects homes and transport BBC 9 August 2019 Retrieved 9 August 2019 a b c d https www nationalgrideso com document 151081 download Interim Report into the Low Frequency Demand Disconnection LFDD following Generator Trips and Frequency Excursion on 9 Aug 2019 16 August 2019 enappsys 9 August 2019 GB Frequency drops off the chart to Tweet via Twitter Stoker Liam 3 January 2020 Blackout investigation Power firms fined as Ofgem accelerates ESO review Current News Retrieved 8 January 2020 Companies pay 10 5 million over 9 August power cut Ofgem 3 January 2020 Stacey Kiran Adams Christopher 5 November 2015 National Grid in emergency plea for heavy users to power down Financial Times pp front page Further reading EditHannah Leslie 1979 Electricity Before Nationalisation A Study in the Development of the Electricity Supply Industry in Britain to 1948 London amp Basingstoke Macmillan Publishers for the Electricity Council ISBN 0 8018 2145 2 External links Edit Wikimedia Commons has media related to National Grid Great Britain The Transmission System National Grid s Seven Year Statement 2008 The Statement of the Use of System Charging Methodology permanent dead link National Grid Useful Information National Grid National Grid live data ELEXON UK National Grid Status UK Electricity Networks The nature of UK electricity transmission and distribution networks in an intermittent renewable and embedded electricity generation future Scott Butler The electricity supply industry and the Central Electricity Generating Board UK Competition Commission Report 1987 Map of GB power stations and national grid BBC website but map revised by Deloitte amp Touche 2003 Archive Carbon intensity variations in the GB grid Retrieved from https en wikipedia org w index php title National Grid Great Britain amp oldid 1136473596 Control of the grid, wikipedia, wiki, book, books, library,