fbpx
Wikipedia

Synchronous condenser

In electrical engineering, a synchronous condenser (sometimes called a syncon, synchronous capacitor or synchronous compensator) is a DC-excited synchronous motor, whose shaft is not connected to anything but spins freely.[1] Its purpose is not to convert electric power to mechanical power or vice versa, but to adjust conditions on the electric power transmission grid. Its field is controlled by a voltage regulator to either generate or absorb reactive power as needed to adjust the grid's voltage, or to improve power factor. The condenser’s installation and operation are identical to large electric motors and generators (some generators are actually designed to be able to operate as synchronous condensers with the prime mover disconnected[2]).

Synchronous condenser installation at Templestowe substation, Melbourne, Victoria, Australia. Built by ASEA in 1966, the unit is hydrogen cooled and capable of three phase power at 125 MVA.

Increasing the device's field excitation results in its furnishing reactive power (measured in units of var) to the system. Its principal advantage is the ease with which the amount of correction can be adjusted.

Synchronous condensers are an alternative to capacitor banks and static VAR compensators for power-factor correction in power grids.[3] One advantage is that the amount of reactive power from a synchronous condenser can be continuously adjusted. Reactive power from a capacitor bank decreases when grid voltage decreases while the reactive power from a synchronous condenser inherently increases as voltage decreases.[1] Additionally, synchronous condensers are more tolerant of power fluctuations and severe drops in voltage.[3] However, synchronous machines have higher energy losses than static capacitor banks.[1]

Most synchronous condensers connected to electrical grids are rated between 20 MVAR (megavar) and 200 MVAR and many are hydrogen cooled. There is no explosion hazard as long as the hydrogen concentration is maintained above 70%, typically above 91%.[4] A syncon can be 8 metres long and 5 meters tall, weighing 170 tonnes.[5]

Synchronous condensers also help stabilize grids. The inertial response of the machine and its inductance can help stabilize a power system during rapid fluctuations of loads such as those created by short circuits or electric arc furnaces. For this reason, large installations of synchronous condensers are sometimes used in association with high-voltage direct current converter stations to supply reactive power to the alternating current grid. Synchronous condensers are also finding use in facilitating the switchover between power grids[6] and providing power grid stabilization as turbine-based power generators are replaced with solar and wind energy.[7][3]

Theory edit

 
V curves for a synchronous machine. A synchronous condensor operates at nearly zero real power. As the machine passes from underexcited to overexcited, its stator current passes through a minimum.

A rotating coil [8] in a magnetic field tends to produce a sine-wave voltage. When connected to a circuit some current will flow depending on how the voltage on the system is different from this open-circuit voltage. Note that mechanical torque (produced by a motor, required by a generator) corresponds only to the real power. Reactive power does not result in any torque.

As the mechanical load on a synchronous motor increases, the stator current   increases regardless of the field excitation. For both under- and over-excited motors, the power factor (p.f.) tends to approach unity with increase in mechanical load. This change in power factor is larger than the change in   with increase in load.

The phase of armature current varies with field excitation. The current has larger values for lower and higher values of excitation. In between, the current has minimum value corresponding to a particular excitation (see graph on right). The variations of   with excitation are known as   curves because of their shape.

For the same mechanical load, the armature current varies with field excitation over a wide range and so causes the power factor also to vary accordingly. When over-excited, the motor runs with leading power factor (and supplies vars to the grid) and when under-excited with lagging power factor (and absorbs vars from the grid). In between, the power factor is unity. The minimum armature current corresponds to the point of unity power factor (voltage and current in phase).

As in a synchronous motor, the stator of the machine is connected to a three-phase supply of voltage   (assumed to be constant), and this creates a rotating magnetic field within the machine. Likewise, the rotor is excited with a DC current   to act as an electromagnet. In normal operation the rotor magnet follows the stator field at synchronous speed. The rotating electromagnet induces a three-phase voltage   in the stator windings as if the machine were a synchronous generator. If the machine is considered to be ideal, with no mechanical, magnetic, or electrical losses, its equivalent circuit will be an AC generator in series with the winding inductance   of the stator. The magnitude of   depends on the excitation current   and the speed of rotation, and as the latter is fixed,   depends only on  . If   is critically adjusted to a value  ,   will be equal and opposite to  , and the current in the stator   will be zero. This corresponds to the minimum in the curve shown above. If, however,   is increased above  ,   will exceed  , and the difference is accounted for by a voltage   appearing across the stator inductance  :   where   is the stator reactance. Now the stator current   is no longer zero. Since the machine is ideal,  ,   and   will all be in phase, and   will be entirely reactive (i.e. in phase quadrature). Viewed from the supply side of the machine's terminals, a negative reactive current will flow out of the terminals, and the machine will therefore appear as a capacitor, the magnitude of whose reactance will fall as   increases above  . If   is adjusted to be less than  ,   will exceed  , and a positive reactive current will flow into the machine. The machine will then appear as an inductor whose reactance falls as   is reduced further. These conditions correspond to the two rising arms of the V-curves (above). In a practical machine with losses, the equivalent circuit will contain a resistor in parallel with the terminals to represent mechanical and magnetic losses, and another resistor in series with the generator and L, representing copper losses in the stator. Thus in a practical machine   will contain a small in-phase component, and will not fall to zero.

Application edit

An over-excited synchronous motor has a leading power factor. This makes it useful for power-factor correction of industrial loads. Both transformers and induction motors draw lagging (magnetising) currents from the line. On light loads, the power drawn by induction motors has a large reactive component and the power factor has a low value. The added current flowing to supply reactive power creates additional losses in the power system. In an industrial plant, synchronous motors can be used to supply some of the reactive power required by induction motors. This improves the plant power factor and reduces the reactive current required from the grid.

A synchronous condenser provides stepless automatic power-factor correction with the ability to produce up to 150% additional vars. The system produces no switching transients and is not affected by system electrical harmonics (some harmonics can even be absorbed by synchronous condensers). They will not produce excessive voltage levels and are not susceptible to electrical resonances. Because of the rotating inertia of the synchronous condenser, it can provide limited voltage support during very short power drops.

Rotating synchronous condensers were introduced in 1930s[2] and were common in 1950s, but due to high costs were eventually displaced in new installations by the static var compensators (SVCs).[2] They remain an alternative (or a supplement) to capacitors for power-factor correction because of problems that have been experienced with harmonics causing capacitor overheating and catastrophic failures. Synchronous condensers are also useful for supporting voltage levels. The reactive power produced by a capacitor bank is in direct proportion to the square of its terminal voltage, and if the system voltage decreases, the capacitors produce less reactive power, when it is most needed,[2] while if the system voltage increases the capacitors produce more reactive power, which exacerbates the problem. In contrast, with a constant field, a synchronous condenser naturally supplies more reactive power to a low voltage and absorbs more reactive power from a high voltage, plus the field can be controlled. This reactive power improves voltage regulation in situations such as when starting large motors, or where power must travel long distances from where it is generated to where it is used, as is the case with power wheeling, the transmission of electric power from one geographic region to another within a set of interconnected electric power systems.

When compared to an SVC, the synchronous condenser has a few advantages:[2]

  • the rotational inertia allows it to ride-through the short circuit condition;
  • reactive power delivery does not depend on the line voltage;
  • it is relatively insensitive to overloads and typically can operate for half an hour at 110-120% of capacity and can briefly deliver up to 200% of rated reactive power.

Synchronous condensers may also be referred to as Dynamic Power Factor Correction systems. These machines can prove very effective when advanced controls are utilized. A PLC based controller with PF controller and regulator will allow the system to be set to meet a given power factor or can be set to produce a specified amount of reactive power.

On electric power systems, synchronous condensers can be used to control the voltage on long transmission lines, especially for lines with a relatively high ratio of inductive reactance to resistance.[9]

In addition to purpose-built units, existing steam or combustion turbines can be retrofit for use as a syncon. In this situation, the turbine can be retrofit with either an auxiliary starting motor, use the existing generator as an electric means of startup, or a synchronous self-shifting (SSS) clutch with the existing turbine/fuel source.[10] Using a separate starter motor is usually recommended instead of the existing generator for startup, as the generator shaft/coupling generally can't withstand the torques imposed on them during startup. Using purely electric startup methods, the syncon relies on the starter motor to provide an initial startup, and the generator or auxiliary motor provide the system with the necessary rotational inertia to produce reactive power. With the SSS clutch retrofit, the existing turbine setup is largely reused. Here, the turbine uses its existing fuel source to start and sync to the grid, which is when the SSS clutch disconnects the turbine and generator. The generator thus uses grid energy to keep spinning, to provide leading or lagging reactive power as needed. Each setup has its own advantages and disadvantages: the electric drive only systems do not require combustion from the old turbines, where an old generation system would generally produce more emissions than a newer one of the same fuel type while the combustion driven system would have the ability to alternate between generating real and reactive power as needed.[11]

Gallery edit

See also edit

References edit

  1. ^ a b c B. M. Weedy, Electric Power Systems Second Edition, John Wiley and Sons, London, 1972, ISBN 0-471-92445-8 page 149
  2. ^ a b c d e Kundur 1994, p. 638.
  3. ^ a b c Fairley, Peter (2015-07-24). "Zombie Coal Plants Reanimated to Stabilize the Grid". IEEE Spectrum. IEEE. Retrieved 2023-11-13.
  4. ^ "All About Circuits".
  5. ^ Parkinson, Giles (25 October 2021). "Wind and solar limits relaxed after four big spinning machines installed". RenewEconomy. from the original on 26 October 2021.
  6. ^ Fairley, Peter (2023-11-13). "To Free The Baltic Grid, Old Technology Is New Again". IEEE Spectrum. IEEE. Retrieved 2023-11-13.
  7. ^ "GE synchronous condensers – 100 years on". Modern Power Systems. 2020-02-12. Retrieved 2023-11-13.
  8. ^ http://www.pscpower.com/wp-content/uploads/2013/06/Power-Factor.pdf [bare URL PDF]
  9. ^ Donald Fink, Wayne Beaty (ed) Standard Handbook for Electrical Engineers Eleventh Edition, Mc Graw Hill, 1978, ISBN 0-07-020974-X, page 14-33
  10. ^ POWER (2020-09-01). "Putting Idle Turbine Generators to Work". POWER Magazine. Retrieved 2023-01-13.
  11. ^ Directors, Clarion Energy Content (2011-10-01). "Converting Existing Synchronous Generators into Synchronous Condensers". Power Engineering. Retrieved 2023-01-13.

Sources edit

  • Kundur, Prabha (22 January 1994). "Reactive Power and Voltage Control" (PDF). Power System Stability and Control. McGraw-Hill Education. pp. 627–687. ISBN 978-0-07-035958-1. OCLC 1054007373.

External links edit

  • A Short Course on Synchronous Machines and Synchronous Condensers

synchronous, condenser, electrical, engineering, synchronous, condenser, sometimes, called, syncon, synchronous, capacitor, synchronous, compensator, excited, synchronous, motor, whose, shaft, connected, anything, spins, freely, purpose, convert, electric, pow. In electrical engineering a synchronous condenser sometimes called a syncon synchronous capacitor or synchronous compensator is a DC excited synchronous motor whose shaft is not connected to anything but spins freely 1 Its purpose is not to convert electric power to mechanical power or vice versa but to adjust conditions on the electric power transmission grid Its field is controlled by a voltage regulator to either generate or absorb reactive power as needed to adjust the grid s voltage or to improve power factor The condenser s installation and operation are identical to large electric motors and generators some generators are actually designed to be able to operate as synchronous condensers with the prime mover disconnected 2 Synchronous condenser installation at Templestowe substation Melbourne Victoria Australia Built by ASEA in 1966 the unit is hydrogen cooled and capable of three phase power at 125 MVA Increasing the device s field excitation results in its furnishing reactive power measured in units of var to the system Its principal advantage is the ease with which the amount of correction can be adjusted Synchronous condensers are an alternative to capacitor banks and static VAR compensators for power factor correction in power grids 3 One advantage is that the amount of reactive power from a synchronous condenser can be continuously adjusted Reactive power from a capacitor bank decreases when grid voltage decreases while the reactive power from a synchronous condenser inherently increases as voltage decreases 1 Additionally synchronous condensers are more tolerant of power fluctuations and severe drops in voltage 3 However synchronous machines have higher energy losses than static capacitor banks 1 Most synchronous condensers connected to electrical grids are rated between 20 MVAR megavar and 200 MVAR and many are hydrogen cooled There is no explosion hazard as long as the hydrogen concentration is maintained above 70 typically above 91 4 A syncon can be 8 metres long and 5 meters tall weighing 170 tonnes 5 Synchronous condensers also help stabilize grids The inertial response of the machine and its inductance can help stabilize a power system during rapid fluctuations of loads such as those created by short circuits or electric arc furnaces For this reason large installations of synchronous condensers are sometimes used in association with high voltage direct current converter stations to supply reactive power to the alternating current grid Synchronous condensers are also finding use in facilitating the switchover between power grids 6 and providing power grid stabilization as turbine based power generators are replaced with solar and wind energy 7 3 Contents 1 Theory 2 Application 3 Gallery 4 See also 5 References 6 Sources 7 External linksTheory edit nbsp V curves for a synchronous machine A synchronous condensor operates at nearly zero real power As the machine passes from underexcited to overexcited its stator current passes through a minimum A rotating coil 8 in a magnetic field tends to produce a sine wave voltage When connected to a circuit some current will flow depending on how the voltage on the system is different from this open circuit voltage Note that mechanical torque produced by a motor required by a generator corresponds only to the real power Reactive power does not result in any torque As the mechanical load on a synchronous motor increases the stator current I a displaystyle I a nbsp increases regardless of the field excitation For both under and over excited motors the power factor p f tends to approach unity with increase in mechanical load This change in power factor is larger than the change in I a displaystyle I a nbsp with increase in load The phase of armature current varies with field excitation The current has larger values for lower and higher values of excitation In between the current has minimum value corresponding to a particular excitation see graph on right The variations of I displaystyle I nbsp with excitation are known as V displaystyle V nbsp curves because of their shape For the same mechanical load the armature current varies with field excitation over a wide range and so causes the power factor also to vary accordingly When over excited the motor runs with leading power factor and supplies vars to the grid and when under excited with lagging power factor and absorbs vars from the grid In between the power factor is unity The minimum armature current corresponds to the point of unity power factor voltage and current in phase As in a synchronous motor the stator of the machine is connected to a three phase supply of voltage V s displaystyle V s nbsp assumed to be constant and this creates a rotating magnetic field within the machine Likewise the rotor is excited with a DC current I e displaystyle I e nbsp to act as an electromagnet In normal operation the rotor magnet follows the stator field at synchronous speed The rotating electromagnet induces a three phase voltage V g displaystyle V g nbsp in the stator windings as if the machine were a synchronous generator If the machine is considered to be ideal with no mechanical magnetic or electrical losses its equivalent circuit will be an AC generator in series with the winding inductance L displaystyle L nbsp of the stator The magnitude of V g displaystyle V g nbsp depends on the excitation current I e displaystyle I e nbsp and the speed of rotation and as the latter is fixed V g displaystyle V g nbsp depends only on I e displaystyle I e nbsp If I e displaystyle I e nbsp is critically adjusted to a value I e0 displaystyle I text e0 nbsp V g displaystyle V g nbsp will be equal and opposite to V s displaystyle V s nbsp and the current in the stator I s displaystyle I s nbsp will be zero This corresponds to the minimum in the curve shown above If however I e displaystyle I e nbsp is increased above I e0 displaystyle I text e0 nbsp V g displaystyle V g nbsp will exceed V s displaystyle V s nbsp and the difference is accounted for by a voltage V 1 displaystyle V 1 nbsp appearing across the stator inductance L displaystyle L nbsp V L I s X L displaystyle V L I s X L nbsp where X L displaystyle X L nbsp is the stator reactance Now the stator current I s displaystyle I s nbsp is no longer zero Since the machine is ideal V g displaystyle V g nbsp V L displaystyle V L nbsp and V s displaystyle V s nbsp will all be in phase and I s displaystyle I s nbsp will be entirely reactive i e in phase quadrature Viewed from the supply side of the machine s terminals a negative reactive current will flow out of the terminals and the machine will therefore appear as a capacitor the magnitude of whose reactance will fall as I r displaystyle I r nbsp increases above I s0 displaystyle I text s0 nbsp If I e displaystyle I e nbsp is adjusted to be less than I e0 displaystyle I text e0 nbsp V s displaystyle V s nbsp will exceed V g displaystyle V g nbsp and a positive reactive current will flow into the machine The machine will then appear as an inductor whose reactance falls as I e displaystyle I e nbsp is reduced further These conditions correspond to the two rising arms of the V curves above In a practical machine with losses the equivalent circuit will contain a resistor in parallel with the terminals to represent mechanical and magnetic losses and another resistor in series with the generator and L representing copper losses in the stator Thus in a practical machine I s displaystyle I s nbsp will contain a small in phase component and will not fall to zero Application editAn over excited synchronous motor has a leading power factor This makes it useful for power factor correction of industrial loads Both transformers and induction motors draw lagging magnetising currents from the line On light loads the power drawn by induction motors has a large reactive component and the power factor has a low value The added current flowing to supply reactive power creates additional losses in the power system In an industrial plant synchronous motors can be used to supply some of the reactive power required by induction motors This improves the plant power factor and reduces the reactive current required from the grid A synchronous condenser provides stepless automatic power factor correction with the ability to produce up to 150 additional vars The system produces no switching transients and is not affected by system electrical harmonics some harmonics can even be absorbed by synchronous condensers They will not produce excessive voltage levels and are not susceptible to electrical resonances Because of the rotating inertia of the synchronous condenser it can provide limited voltage support during very short power drops Rotating synchronous condensers were introduced in 1930s 2 and were common in 1950s but due to high costs were eventually displaced in new installations by the static var compensators SVCs 2 They remain an alternative or a supplement to capacitors for power factor correction because of problems that have been experienced with harmonics causing capacitor overheating and catastrophic failures Synchronous condensers are also useful for supporting voltage levels The reactive power produced by a capacitor bank is in direct proportion to the square of its terminal voltage and if the system voltage decreases the capacitors produce less reactive power when it is most needed 2 while if the system voltage increases the capacitors produce more reactive power which exacerbates the problem In contrast with a constant field a synchronous condenser naturally supplies more reactive power to a low voltage and absorbs more reactive power from a high voltage plus the field can be controlled This reactive power improves voltage regulation in situations such as when starting large motors or where power must travel long distances from where it is generated to where it is used as is the case with power wheeling the transmission of electric power from one geographic region to another within a set of interconnected electric power systems When compared to an SVC the synchronous condenser has a few advantages 2 the rotational inertia allows it to ride through the short circuit condition reactive power delivery does not depend on the line voltage it is relatively insensitive to overloads and typically can operate for half an hour at 110 120 of capacity and can briefly deliver up to 200 of rated reactive power Synchronous condensers may also be referred to as Dynamic Power Factor Correction systems These machines can prove very effective when advanced controls are utilized A PLC based controller with PF controller and regulator will allow the system to be set to meet a given power factor or can be set to produce a specified amount of reactive power On electric power systems synchronous condensers can be used to control the voltage on long transmission lines especially for lines with a relatively high ratio of inductive reactance to resistance 9 In addition to purpose built units existing steam or combustion turbines can be retrofit for use as a syncon In this situation the turbine can be retrofit with either an auxiliary starting motor use the existing generator as an electric means of startup or a synchronous self shifting SSS clutch with the existing turbine fuel source 10 Using a separate starter motor is usually recommended instead of the existing generator for startup as the generator shaft coupling generally can t withstand the torques imposed on them during startup Using purely electric startup methods the syncon relies on the starter motor to provide an initial startup and the generator or auxiliary motor provide the system with the necessary rotational inertia to produce reactive power With the SSS clutch retrofit the existing turbine setup is largely reused Here the turbine uses its existing fuel source to start and sync to the grid which is when the SSS clutch disconnects the turbine and generator The generator thus uses grid energy to keep spinning to provide leading or lagging reactive power as needed Each setup has its own advantages and disadvantages the electric drive only systems do not require combustion from the old turbines where an old generation system would generally produce more emissions than a newer one of the same fuel type while the combustion driven system would have the ability to alternate between generating real and reactive power as needed 11 Gallery editSynchronous condenser unit at Templestowe substation Victoria Australia nbsp Side view of the condenser unit nbsp Front end of condenser unit nbsp Section view showing interior construction of condenser nbsp Information plate showing technical specifications of condenser unitExample 1See also editStatic synchronous compensator Static VAR compensator Unified power flow controllerReferences edit a b c B M Weedy Electric Power Systems Second Edition John Wiley and Sons London 1972 ISBN 0 471 92445 8 page 149 a b c d e Kundur 1994 p 638 a b c Fairley Peter 2015 07 24 Zombie Coal Plants Reanimated to Stabilize the Grid IEEE Spectrum IEEE Retrieved 2023 11 13 All About Circuits Parkinson Giles 25 October 2021 Wind and solar limits relaxed after four big spinning machines installed RenewEconomy Archived from the original on 26 October 2021 Fairley Peter 2023 11 13 To Free The Baltic Grid Old Technology Is New Again IEEE Spectrum IEEE Retrieved 2023 11 13 GE synchronous condensers 100 years on Modern Power Systems 2020 02 12 Retrieved 2023 11 13 http www pscpower com wp content uploads 2013 06 Power Factor pdf bare URL PDF Donald Fink Wayne Beaty ed Standard Handbook for Electrical Engineers Eleventh Edition Mc Graw Hill 1978 ISBN 0 07 020974 X page 14 33 POWER 2020 09 01 Putting Idle Turbine Generators to Work POWER Magazine Retrieved 2023 01 13 Directors Clarion Energy Content 2011 10 01 Converting Existing Synchronous Generators into Synchronous Condensers Power Engineering Retrieved 2023 01 13 Sources editKundur Prabha 22 January 1994 Reactive Power and Voltage Control PDF Power System Stability and Control McGraw Hill Education pp 627 687 ISBN 978 0 07 035958 1 OCLC 1054007373 External links edit nbsp Wikimedia Commons has media related to Synchronous condensers A Short Course on Synchronous Machines and Synchronous Condensers Retrieved from https en wikipedia org w index php title Synchronous condenser amp oldid 1200183774, wikipedia, wiki, book, books, library,

article

, read, download, free, free download, mp3, video, mp4, 3gp, jpg, jpeg, gif, png, picture, music, song, movie, book, game, games.