fbpx
Wikipedia

Polarity (mutual inductance)

In electrical engineering, dot marking convention, or alphanumeric marking convention, or both, can be used to denote the same relative instantaneous polarity of two mutually inductive components such as between transformer windings. These markings may be found on transformer cases beside terminals, winding leads, nameplates, schematic and wiring diagrams.

An instrument transformer, looking at the high voltage side with dot convention and H1 marking.
The low voltage side of the instrument transformer, with dot and X1 marking. The X1 and H1 terminals are adjacent.

The convention is that current entering a transformer at the end of a winding marked with a dot, will tend to produce current exiting other windings at their dotted ends.[citation needed]

Maintaining proper polarity is important in power system protection, measurement and control systems. A reversed instrument transformer winding may defeat protective relays, give inaccurate power and energy measurements, or result in display of negative power factor. Reversed connections of paralleled transformer windings will cause circulating currents or an effective short circuit. In signal circuits, reversed connections of transformer windings can result in incorrect operation of amplifiers and speaker systems, or cancellation of signals that are meant to add.

Polarity edit

Leads of primary and secondary windings are said to be of the same polarity when instantaneous current entering the primary winding lead results in instantaneous current leaving the secondary winding lead as though the two leads were a continuous circuit.[1][2] In the case of two windings wound around the same core in parallel, for example, the polarity will be the same on the same ends: A sudden (instantaneous) current in the first coil will induce a voltage opposing the sudden increase (Lenz's law) in the first and also in the second coil, because the magnetic field produced by the current in the first coil traverses the two coils in the same manner. The second coil will, therefore, show an induced current opposite in direction to the inducing current in the first coil. Both leads behave like a continuous circuit, one current entering into the first lead and another current leaving the second lead.

Transformer windings edit

Two methods are commonly used to denote which terminals present the same relative polarity. A dot may be used, or an alphanumeric designation. Alphanumeric designations are typically in the form H1 for primaries, and for secondaries, X1, (and Y1, Z1, if more windings present).

Unlike single-phase transformers, three-phase transformers may have a phase shift due to different winding configurations (for example, a wye connected primary and a delta connected secondary), resulting in a multiple of 30 degree phase shift between H1 and X1 bushing designations. The vector group in the nameplate of the transformer gives information about such phase shift.

Terminal layout conventions edit

Transformers are said to have "additive" or "subtractive" polarity based on their physical arrangement of terminals and the polarity of windings connected to the terminals. The convention used for North American transformers is that, facing the high voltage side of the transformer, the H1 terminal is on the observer's right. A transformer is called "additive" if, conceptually, connecting the high-voltage terminal to the adjacent low-voltage terminal gives a total voltage between the other two terminals that is the sum of the high voltage and low voltage ratings, when the high-voltage winding is excited at rated voltage. The H1 and X2 terminals are physically adjacent. In the "subtractive" arrangement, the H1 and X1 terminals are adjacent, and the voltage measured between H2 and X2 would be the difference of the high voltage and low voltage windings.[3] Pole mounted distribution transformers are manufactured with additive polarity, while instrument transformers are made with subtractive polarity. Where markings have been obscured or are suspect, a test can be made by interconnecting the windings and exciting the transformer, and measuring the voltages.[4]

Three phase transformers edit

Three-phase transformers used in electric power systems will have a nameplate that indicate the phase relationships between their terminals. This may be in the form of a phasor diagram, or using an alpha-numeric code to show the type of internal connection (wye or delta) for each winding.

See also edit

References edit

  1. ^ Knowlton, Archer E., ed. (1949). Standard Handbook for Electrical Engineers (8 ed.). McGraw-Hill. pp. 552 §6-15, p. 606 §6-162.
  2. ^ Alexander, Charles (2009). Fundamentals of electric circuits. McGraw-Hill. pp. 559–560. ISBN 978-0-07352955-4.
  3. ^ Croft, Terrell; Summers, Wilford (1987). American Electricians' Handbook (11 ed.). McGraw-Hill. pp. 5-44–5-45. ISBN 0-07-013932-6.
  4. ^ "Transformer Polarity" (PDF). Kilowatt Classroom, LLC. 2002. (PDF) from the original on 2022-07-03. Retrieved 2018-01-16. (4 pages)

Further reading edit

  • Brenner, Egon; Javid, Mansour (1959). "§18.1 'Symbols and Polarity of Mutual Inductance' in Chapter 18 - Circuits with Magnetic Circuits". Analysis of Electric Circuits. McGraw-Hill Electrical and Electronic Engineering Series. McGraw-Hill. pp. 589–590. Retrieved 2022-07-03.
  • Harman, Willis W.; Lytle, Dean W. (1962). "10-2. Transformers". Electrical and Mechanical Networks: An introduction to their analysis. McGraw-Hill Electrical and Electronic Engineering Series (1 ed.). New York, USA: McGraw-Hill Book Company, Inc. / The Maple Press Company, York, PA. pp. 353–354. LCCN 61-17340. Order No. 26590. p. 354: The voltage drop from the dotted to the undotted end of a coil, induced by a current i flowing in at the dotted end of the other coil, is M di/dt. If M is assumed positive, the four markings of Fig. 10-3a. correspond exactly and may be freely interchanged. The same holds true for the four markings of Fig. 10-3b.
  • Grossner, Nathan (1967). Transformers for Electronic Circuits. McGraw-Hill. p. 26. ISBN 0-07024979-2.
  • Nahvi, Mahmood; Edminister, Joseph (2002). Schaum's outline of theory and problems of electric circuits. Schaum's outline of theory and problems / Schaum's outline series (4 ed.). McGraw-Hill Professional. p. 338. ISBN 0-07-139307-2. Retrieved 2022-07-03.
  • Boylestad, Robert L. (2003). "Section 21.8: Series connection of mutually coupled coils". Introductory Circuit Analysis (10 ed.). Prentice Hall. p. 954. ISBN 0-13-097417-X. Retrieved 2022-07-03.
  • Parker, Martin R.; Ula, Sadrul; Webb, William E. (2005). "§2.5.5 'Transformers' & §10.1.3 'The Ideal Transformer'". In Whitaker, Jerry C. (ed.). The Electronics Handbook (2 ed.). Taylor & Francis. pp. 172, 1017. ISBN 0-8493-1889-0. Retrieved 2022-07-03.
  • Kothari, Dwarkadas Prahladadas; Nagrath, Inder Jit (2010). "Chapter 3 - Transformers". Electric machines (4 ed.). Tata McGraw-Hill. p. 73, §3.7 'Transformer Testing'. ISBN 978-0-07-069967-0. Retrieved 2022-07-03.
  • ANSI/IEEE C57.13, American National Standard Requirements for Instrument Transformers.

polarity, mutual, inductance, this, article, about, magnetically, coupled, transformer, winding, polarities, motor, winding, polarity, electric, motor, convention, redirects, here, similar, terms, notation, disambiguation, electrical, engineering, marking, con. This article is about magnetically coupled transformer winding polarities For motor winding polarity see Electric motor Dot convention redirects here For similar terms see Dot notation disambiguation In electrical engineering dot marking convention or alphanumeric marking convention or both can be used to denote the same relative instantaneous polarity of two mutually inductive components such as between transformer windings These markings may be found on transformer cases beside terminals winding leads nameplates schematic and wiring diagrams An instrument transformer looking at the high voltage side with dot convention and H1 marking The low voltage side of the instrument transformer with dot and X1 marking The X1 and H1 terminals are adjacent The convention is that current entering a transformer at the end of a winding marked with a dot will tend to produce current exiting other windings at their dotted ends citation needed Maintaining proper polarity is important in power system protection measurement and control systems A reversed instrument transformer winding may defeat protective relays give inaccurate power and energy measurements or result in display of negative power factor Reversed connections of paralleled transformer windings will cause circulating currents or an effective short circuit In signal circuits reversed connections of transformer windings can result in incorrect operation of amplifiers and speaker systems or cancellation of signals that are meant to add Contents 1 Polarity 2 Transformer windings 3 Terminal layout conventions 4 Three phase transformers 5 See also 6 References 7 Further readingPolarity editLeads of primary and secondary windings are said to be of the same polarity when instantaneous current entering the primary winding lead results in instantaneous current leaving the secondary winding lead as though the two leads were a continuous circuit 1 2 In the case of two windings wound around the same core in parallel for example the polarity will be the same on the same ends A sudden instantaneous current in the first coil will induce a voltage opposing the sudden increase Lenz s law in the first and also in the second coil because the magnetic field produced by the current in the first coil traverses the two coils in the same manner The second coil will therefore show an induced current opposite in direction to the inducing current in the first coil Both leads behave like a continuous circuit one current entering into the first lead and another current leaving the second lead Transformer windings editTwo methods are commonly used to denote which terminals present the same relative polarity A dot may be used or an alphanumeric designation Alphanumeric designations are typically in the form H1 for primaries and for secondaries X1 and Y1 Z1 if more windings present Unlike single phase transformers three phase transformers may have a phase shift due to different winding configurations for example a wye connected primary and a delta connected secondary resulting in a multiple of 30 degree phase shift between H1 and X1 bushing designations The vector group in the nameplate of the transformer gives information about such phase shift Terminal layout conventions editTransformers are said to have additive or subtractive polarity based on their physical arrangement of terminals and the polarity of windings connected to the terminals The convention used for North American transformers is that facing the high voltage side of the transformer the H1 terminal is on the observer s right A transformer is called additive if conceptually connecting the high voltage terminal to the adjacent low voltage terminal gives a total voltage between the other two terminals that is the sum of the high voltage and low voltage ratings when the high voltage winding is excited at rated voltage The H1 and X2 terminals are physically adjacent In the subtractive arrangement the H1 and X1 terminals are adjacent and the voltage measured between H2 and X2 would be the difference of the high voltage and low voltage windings 3 Pole mounted distribution transformers are manufactured with additive polarity while instrument transformers are made with subtractive polarity Where markings have been obscured or are suspect a test can be made by interconnecting the windings and exciting the transformer and measuring the voltages 4 Three phase transformers editThree phase transformers used in electric power systems will have a nameplate that indicate the phase relationships between their terminals This may be in the form of a phasor diagram or using an alpha numeric code to show the type of internal connection wye or delta for each winding See also editElectrical polarityReferences edit Knowlton Archer E ed 1949 Standard Handbook for Electrical Engineers 8 ed McGraw Hill pp 552 6 15 p 606 6 162 Alexander Charles 2009 Fundamentals of electric circuits McGraw Hill pp 559 560 ISBN 978 0 07352955 4 Croft Terrell Summers Wilford 1987 American Electricians Handbook 11 ed McGraw Hill pp 5 44 5 45 ISBN 0 07 013932 6 Transformer Polarity PDF Kilowatt Classroom LLC 2002 Archived PDF from the original on 2022 07 03 Retrieved 2018 01 16 4 pages Further reading editBrenner Egon Javid Mansour 1959 18 1 Symbols and Polarity of Mutual Inductance in Chapter 18 Circuits with Magnetic Circuits Analysis of Electric Circuits McGraw Hill Electrical and Electronic Engineering Series McGraw Hill pp 589 590 Retrieved 2022 07 03 Harman Willis W Lytle Dean W 1962 10 2 Transformers Electrical and Mechanical Networks An introduction to their analysis McGraw Hill Electrical and Electronic Engineering Series 1 ed New York USA McGraw Hill Book Company Inc The Maple Press Company York PA pp 353 354 LCCN 61 17340 Order No 26590 p 354 The voltage drop from the dotted to the undotted end of a coil induced by a current i flowing in at the dotted end of the other coil is M di dt If M is assumed positive the four markings of Fig 10 3a correspond exactly and may be freely interchanged The same holds true for the four markings of Fig 10 3b Grossner Nathan 1967 Transformers for Electronic Circuits McGraw Hill p 26 ISBN 0 07024979 2 Nahvi Mahmood Edminister Joseph 2002 Schaum s outline of theory and problems of electric circuits Schaum s outline of theory and problems Schaum s outline series 4 ed McGraw Hill Professional p 338 ISBN 0 07 139307 2 Retrieved 2022 07 03 Boylestad Robert L 2003 Section 21 8 Series connection of mutually coupled coils Introductory Circuit Analysis 10 ed Prentice Hall p 954 ISBN 0 13 097417 X Retrieved 2022 07 03 Parker Martin R Ula Sadrul Webb William E 2005 2 5 5 Transformers amp 10 1 3 The Ideal Transformer In Whitaker Jerry C ed The Electronics Handbook 2 ed Taylor amp Francis pp 172 1017 ISBN 0 8493 1889 0 Retrieved 2022 07 03 Kothari Dwarkadas Prahladadas Nagrath Inder Jit 2010 Chapter 3 Transformers Electric machines 4 ed Tata McGraw Hill p 73 3 7 Transformer Testing ISBN 978 0 07 069967 0 Retrieved 2022 07 03 ANSI IEEE C57 13 American National Standard Requirements for Instrument Transformers Retrieved from https en wikipedia org w index php title Polarity mutual inductance amp oldid 1096295491, wikipedia, wiki, book, books, library,

article

, read, download, free, free download, mp3, video, mp4, 3gp, jpg, jpeg, gif, png, picture, music, song, movie, book, game, games.