fbpx
Wikipedia

Harmonics (electrical power)

In an electric power system, a harmonic of a voltage or current waveform is a sinusoidal wave whose frequency is an integer multiple of the fundamental frequency. Harmonic frequencies are produced by the action of non-linear loads such as rectifiers, discharge lighting, or saturated electric machines. They are a frequent cause of power quality problems and can result in increased equipment and conductor heating, misfiring in variable speed drives, and torque pulsations in motors and generators.

Harmonics are usually classified by two different criteria: the type of signal (voltage or current), and the order of the harmonic (even, odd, triplen, or non-triplen odd); in a three-phase system, they can be further classified according to their phase sequence (positive, negative, zero).

Current harmonics edit

In a normal alternating current power system, the current varies sinusoidally at a specific frequency, usually 50 or 60 hertz. When a linear time-invariant electrical load is connected to the system, it draws a sinusoidal current at the same frequency as the voltage (though usually not in phase with the voltage).[1]: 2  Current harmonics are caused by non-linear loads. When a non-linear load, such as a rectifier is connected to the system, it draws a current that is not necessarily sinusoidal. The current waveform distortion can be quite complex, depending on the type of load and its interaction with other components of the system. Regardless of how complex the current waveform becomes, the Fourier series transform makes it possible to deconstruct the complex waveform into a series of simple sinusoids, which start at the power system fundamental frequency and occur at integer multiples of the fundamental frequency.

In power systems, harmonics are defined as positive integer multiples of the fundamental frequency. Thus, the third harmonic is the third multiple of the fundamental frequency.

Harmonics in power systems are generated by non-linear loads. Semiconductor devices like transistors, IGBTs, MOSFETS, diodes etc are all non-linear loads. Further examples of non-linear loads include common office equipment such as computers and printers, fluorescent lighting, battery chargers and also variable-speed drives. Electric motors do not normally contribute significantly to harmonic generation. Both motors and transformers will however create harmonics when they are over-fluxed or saturated.

Non-linear load currents create distortion in the pure sinusoidal voltage waveform supplied by the utility, and this may result in resonance. The even harmonics do not normally exist in power system due to symmetry between the positive- and negative- halves of a cycle. Further, if the waveforms of the three phases are symmetrical, the harmonic multiples of three are suppressed by delta (Δ) connection of transformers and motors as described below.

If we focus for example on only the third harmonic, we can see how all harmonics with a multiple of three behaves in powers systems.[2]

 
3rd Order Harmonic Addition

Power is supplied by a three phase system, where each phase is 120 degrees apart. This is done for two reasons: mainly because three-phase generators and motors are simpler to construct due to constant torque developed across the three phase phases; and secondly, if the three phases are balanced, they sum to zero, and the size of neutral conductors can be reduced or even omitted in some cases. Both these measures results in significant costs savings to utility companies. However, the balanced third harmonic current will not add to zero in the neutral. As seen in the figure, the 3rd harmonic will add constructively across the three phases. This leads to a current in the neutral wire at three times the fundamental frequency, which can cause problems if the system is not designed for it, (i.e. conductors sized only for normal operation.)[2] To reduce the effect of the third order harmonics delta connections are used as attenuators, or third harmonic shorts as the current circulates in the delta the connection instead of flowing in the neutral of a Y-Δ transformer (wye connection).

 
A compact fluorescent lamp is one example of an electrical load with a non-linear characteristic, due to the rectifier circuit it uses. The current waveform, blue, is highly distorted.

Voltage harmonics edit

Voltage harmonics are mostly caused by current harmonics. The voltage provided by the voltage source will be distorted by current harmonics due to source impedance. If the source impedance of the voltage source is small, current harmonics will cause only small voltage harmonics. It is typically the case that voltage harmonics are indeed small compared to current harmonics. For that reason, the voltage waveform can usually be approximated by the fundamental frequency of voltage. If this approximation is used, current harmonics produce no effect on the real power transferred to the load. An intuitive way to see this comes from sketching the voltage wave at fundamental frequency and overlaying a current harmonic with no phase shift (in order to more easily observe the following phenomenon). What can be observed is that for every period of voltage, there is equal area above the horizontal axis and below the current harmonic wave as there is below the axis and above the current harmonic wave. This means that the average real power contributed by current harmonics is equal to zero. However, if higher harmonics of voltage are considered, then current harmonics do make a contribution to the real power transferred to the load.

A set of three line (or line-to-line) voltages in a balanced three-phase (three-wire or four-wire) power system cannot contain harmonics whose frequency is an integer multiple of the frequency of the third harmonics (i.e. harmonics of order  ), which includes triplen harmonics (i.e. harmonics of order  ).[3] This occurs because otherwise Kirchhoff's voltage law (KVL) would be violated: such harmonics are in phase, so their sum for the three phases is not zero, however KVL requires the sum of such voltages to be zero, which requires the sum of such harmonics to be also zero. With the same argument, a set of three line currents in a balanced three-wire three-phase power system cannot contain harmonics whose frequency is an integer multiple of the frequency of the third harmonics; but a four-wire system can, and the triplen harmonics of the line currents would constitute the neutral current.

Even, odd, triplen and non-triplen odd harmonics edit

The harmonics of a distorted (non-sinusoidal) periodic signal can be classified according to their order.

The cyclic frequency (in hertz) of the harmonics are usually written as   or  , and they are equal to   or  , where   or   is the order of the harmonics (which are integer numbers) and   is the fundamental cyclic frequency of the distorted (non-sinusoidal) periodic signal. Similarly, the angular frequency (in radians per second) of the harmonics are written as   or  , and they are equal to   or  , where   is the fundamental angular frequency of the distorted (non-sinusoidal) periodic signal. The angular frequency is related to the cyclic frequency as   (valid for harmonics as well as the fundamental component).

Even harmonics edit

The even harmonics of a distorted (non-sinusoidal) periodic signal are harmonics whose frequency is a non-zero even integer multiple of the fundamental frequency of the distorted signal (which is the same as the frequency of the fundamental component). So, their order is given by:

 

where   is an integer number; for example,  . If the distorted signal is represented in the trigonometric form or the amplitude-phase form of the Fourier series, then   takes only positive integer values (not including zero), that is it takes values from the set of natural numbers; if the distorted signal is represented in the complex exponential form of the Fourier series, then   takes negative and positive integer values (not including zero, since the DC component is usually not considered as a harmonic).

Odd harmonics edit

The odd harmonics of a distorted (non-sinusoidal) periodic signal are harmonics whose frequency is an odd integer multiple of the fundamental frequency of the distorted signal (which is the same as the frequency of the fundamental component). So, their order is given by:

 

for example,  .

In distorted periodic signals (or waveforms) that possess half-wave symmetry, which means the waveform during the negative half cycle is equal to the negative of the waveform during the positive half cycle, all of the even harmonics are zero ( ) and the DC component is also zero ( ), so they only have odd harmonics ( ); these odd harmonics in general are cosine terms as well as sine terms, but in certain waveforms such as square waves the cosine terms are zero ( ,  ). In many non-linear loads such as inverters, AC voltage controllers and cycloconverters, the output voltage(s) waveform(s) usually has half-wave symmetry and so it only contains odd harmonics.

The fundamental component is an odd harmonic, since when  , the above formula yields  , which is the order of the fundamental component. If the fundamental component is excluded from the odd harmonics, then the order of the remaining harmonics is given by:

 

for example,  .

Triplen harmonics edit

The triplen harmonics of a distorted (non-sinusoidal) periodic signal are harmonics whose frequency is an odd integer multiple of the frequency of the third harmonic(s) of the distorted signal. So, their order is given by:

 

for example,  .

All triplen harmonics are also odd harmonics, but not all odd harmonics are also triplen harmonics.

Non-triplen odd harmonics edit

It is a Certain distorted (non-sinusoidal) periodic signals only possess harmonics that are neither even nor triplen harmonics, for example the output voltage of a three-phase wye-connected AC voltage controller with phase angle control and a firing angle of  and with a purely resistive load connected to its output and fed with three-phase sinusoidal balanced voltages. Their order is given by:

 

for example,  .

All harmonics that are not even harmonics nor triplen harmonics are also odd harmonics, but not all odd harmonics are also harmonics that are not even harmonics nor triplen harmonics.

If the fundamental component is excluded from the harmonics that are not even nor triplen harmonics, then the order of the remaining harmonics is given by:

 

or also by:

 

for example,  . In this latter case, these harmonics are called by IEEE as nontriple odd harmonics.[4]

Positive sequence, negative sequence and zero sequence harmonics edit

In the case of balanced three-phase systems (three-wire or four-wire), the harmonics of a set of three distorted (non-sinusoidal) periodic signals can also be classified according to their phase sequence.[5]: 7–8 [6][3]

Positive sequence harmonics edit

The positive sequence harmonics of a set of three-phase distorted (non-sinusoidal) periodic signals are harmonics that have the same phase sequence as that of the three original signals, and are phase-shifted in time by 120° between each other for a given frequency or order.[7] It can be proven the positive sequence harmonics are harmonics whose order is given by:

 

for example,  .[6][3]

The fundamental components of the three signals are positive sequence harmonics, since when  , the above formula yields  , which is the order of the fundamental components. If the fundamental components are excluded from the positive sequence harmonics, then the order of the remaining harmonics is given by:[5]

 

for example,  .

Negative sequence harmonics edit

The negative sequence harmonics of a set of three-phase distorted (non-sinusoidal) periodic signals are harmonics that have an opposite phase sequence to that of the three original signals, and are phase-shifted in time by 120° for a given frequency or order.[7] It can be proven the negative sequence harmonics are harmonics whose order is given by:[5]

 

for example,  .[6][3]

Zero sequence harmonics edit

The zero sequence harmonics of a set of three-phase distorted (non-sinusoidal) periodic signals are harmonics that are in phase in time for a given frequency or order. It can be proven the zero sequence harmonics are harmonics whose frequency is an integer multiple of the frequency of the third harmonics.[5] So, their order is given by:

 

for example,  .[6][3]

All triplen harmonics are also zero sequence harmonics,[5] but not all zero sequence harmonics are also triplen harmonics.

Total harmonic distortion edit

Total harmonic distortion, or THD is a common measurement of the level of harmonic distortion present in power systems. THD can be related to either current harmonics or voltage harmonics, and it is defined as the ratio of the RMS value of all harmonics to the RMS value of the fundamental component times 100%; the DC component is neglected.

 
 

where Vk is the RMS voltage of the kth harmonic, Ik is the RMS current of the kth harmonic, and k = 1 is the order of the fundamental component.

It is usually the case that we neglect higher voltage harmonics; however, if we do not neglect them, real power transferred to the load is affected by harmonics. Average real power can be found by adding the product of voltage and current (and power factor, denoted by pf here) at each higher frequency to the product of voltage and current at the fundamental frequency, or

 

where Vk and Ik are the RMS voltage and current magnitudes at harmonic k (  denotes the fundamental frequency), and   is the conventional definition of power without factoring in harmonic components.

The power factor mentioned above is the displacement power factor. There is another power factor that depends on THD. True power factor can be taken to mean the ratio between average real power and the magnitude of RMS voltage and current,  .[8]

 

and

 

Substituting this in for the equation for true power factor, it becomes clear that the quantity can be taken to have two components, one of which is the traditional power factor (neglecting the influence of harmonics) and one of which is the harmonics’ contribution to power factor:

 

Names are assigned to the two distinct factors as follows:

 

where   is the displacement power factor and   is the distortion power factor (i.e. the harmonics' contribution to total power factor).

Effects edit

One of the major effects of power system harmonics is to increase the current in the system. This is particularly the case for the third harmonic, which causes a sharp increase in the zero sequence current, and therefore increases the current in the neutral conductor. This effect can require special consideration in the design of an electric system to serve non-linear loads.[9]

In addition to the increased line current, different pieces of electrical equipment can suffer effects from harmonics on the power system.

Motors edit

Electric motors experience losses due to hysteresis and eddy currents set up in the iron core of the motor. These are proportional to the frequency of the current. Since the harmonics are at higher frequencies, they produce higher core losses in a motor than the power frequency would. This results in increased heating of the motor core, which (if excessive) can shorten the life of the motor. The 5th harmonic causes a CEMF (counter electromotive force) in large motors which acts in the opposite direction of rotation. The CEMF is not large enough to counteract the rotation; however it does play a small role in the resulting rotating speed of the motor.

Telephones edit

In the United States, common telephone lines are designed to transmit frequencies between 300 and 3400 Hz. Since electric power in the United States is distributed at 60 Hz, it normally does not interfere with telephone communications because its frequency is too low.

Sources edit

A pure sinusoidal voltage is a conceptual quantity produced by an ideal AC generator built with finely distributed stator and field windings that operate in a uniform magnetic field. Since neither the winding distribution nor the magnetic field are uniform in a working AC machine, voltage waveform distortions are created, and the voltage-time relationship deviates from the pure sine function. The distortion at the point of generation is very small (about 1% to 2%), but nonetheless it exists. Because this is a deviation from a pure sine wave, the deviation is in the form of a periodic function, and by definition, the voltage distortion contains harmonics.

When a sinusoidal voltage is applied to a linear time-invariant load, such as a heating element, the current through it is also sinusoidal. In non-linear and/or time-variant loads, such as an amplifier with a clipping distortion, the voltage swing of the applied sinusoid is limited and the pure tone is polluted with a plethora of harmonics.

When there is significant impedance in the path from the power source to a nonlinear load, these current distortions will also produce distortions in the voltage waveform at the load. However, in most cases where the power delivery system is functioning correctly under normal conditions, the voltage distortions will be quite small and can usually be ignored.

Waveform distortion can be mathematically analysed to show that it is equivalent to superimposing additional frequency components onto a pure sinewave. These frequencies are harmonics (integer multiples) of the fundamental frequency, and can sometimes propagate outwards from nonlinear loads, causing problems elsewhere on the power system.

The classic example of a non-linear load is a rectifier with a capacitor input filter, where the rectifier diode only allows current to pass to the load during the time that the applied voltage exceeds the voltage stored in the capacitor, which might be a relatively small portion of the incoming voltage cycle.

Other examples of nonlinear loads are battery chargers, electronic ballasts, variable frequency drives, and switching mode power supplies.

See also edit

Further reading edit

  • Sankaran, C. (1999-10-01). "Effects of Harmonics on Power Systems". Electrical Construction and Maintenance Magazine. Penton Media, Inc. Retrieved 2020-03-11.

References edit

  1. ^ Das, J. C. (2015). Power System Harmonics and Passive Filter Design. Wiley, IEEE Press. ISBN 978-1-118-86162-2. To distinguish between linear and nonlinear loads, we may say that linear time-invariant loads are characterized so that an application of a sinusoidal voltage results in a sinusoidal flow of current.
  2. ^ a b "Harmonics Made Simple". ecmweb.com. Retrieved 2015-11-25.
  3. ^ a b c d e Wakileh, George J. (2001). Power Systems Harmonics: Fundamentals, Analysis and Filter Design (1 ed.). Springer. pp. 13–15. ISBN 978-3-642-07593-3.
  4. ^ IEEE Standard 519, IEEE recommended practices and requirements for harmonic control in electric power systems, IEEE-519, 1992. p. 10.
  5. ^ a b c d e Das, J. C. (2015). Power System Harmonics and Passive Filter Design. Wiley, IEEE Press. ISBN 978-1-118-86162-2. To distinguish between linear and nonlinear loads, we may say that linear time-invariant loads are characterized so that an application of a sinusoidal voltage results in a sinusoidal flow of current.
  6. ^ a b c d Fuchs, Ewald F.; Masoum, Mohammad A. S. (2008). Power Quality in Power Systems and Electrical Machines (1 ed.). Academic Press. pp. 17–18. ISBN 978-0123695369.
  7. ^ a b Santoso, Surya; Beaty, H. Wayne; Dugan, Roger C.; McGranaghan, Mark F. (2003). Electrical Power Systems Quality (2 ed.). McGraw-Hill. p. 178. ISBN 978-0-07-138622-7.
  8. ^ W. Mack Grady and Robert Gilleski. "Harmonics and How They Relate to Power Factor" (PDF). Proc. of the EPRI Power Quality Issues & Opportunities Conference.
  9. ^ For example, see the National Electrical Code: "A 3-phase, 4-wire, wye-connected power system used to supply power to nonlinear loads may necessitate that the power system design allow for the possibility of high harmonic neutral currents. (Article 220.61(C), FPN No. 2)"

harmonics, electrical, power, this, article, technical, most, readers, understand, please, help, improve, make, understandable, experts, without, removing, technical, details, october, 2019, learn, when, remove, this, message, electric, power, system, harmonic. This article may be too technical for most readers to understand Please help improve it to make it understandable to non experts without removing the technical details October 2019 Learn how and when to remove this message In an electric power system a harmonic of a voltage or current waveform is a sinusoidal wave whose frequency is an integer multiple of the fundamental frequency Harmonic frequencies are produced by the action of non linear loads such as rectifiers discharge lighting or saturated electric machines They are a frequent cause of power quality problems and can result in increased equipment and conductor heating misfiring in variable speed drives and torque pulsations in motors and generators Harmonics are usually classified by two different criteria the type of signal voltage or current and the order of the harmonic even odd triplen or non triplen odd in a three phase system they can be further classified according to their phase sequence positive negative zero Contents 1 Current harmonics 2 Voltage harmonics 3 Even odd triplen and non triplen odd harmonics 3 1 Even harmonics 3 2 Odd harmonics 3 3 Triplen harmonics 3 4 Non triplen odd harmonics 4 Positive sequence negative sequence and zero sequence harmonics 4 1 Positive sequence harmonics 4 2 Negative sequence harmonics 4 3 Zero sequence harmonics 5 Total harmonic distortion 6 Effects 6 1 Motors 6 2 Telephones 7 Sources 8 See also 9 Further reading 10 ReferencesCurrent harmonics editIn a normal alternating current power system the current varies sinusoidally at a specific frequency usually 50 or 60 hertz When a linear time invariant electrical load is connected to the system it draws a sinusoidal current at the same frequency as the voltage though usually not in phase with the voltage 1 2 Current harmonics are caused by non linear loads When a non linear load such as a rectifier is connected to the system it draws a current that is not necessarily sinusoidal The current waveform distortion can be quite complex depending on the type of load and its interaction with other components of the system Regardless of how complex the current waveform becomes the Fourier series transform makes it possible to deconstruct the complex waveform into a series of simple sinusoids which start at the power system fundamental frequency and occur at integer multiples of the fundamental frequency In power systems harmonics are defined as positive integer multiples of the fundamental frequency Thus the third harmonic is the third multiple of the fundamental frequency Harmonics in power systems are generated by non linear loads Semiconductor devices like transistors IGBTs MOSFETS diodes etc are all non linear loads Further examples of non linear loads include common office equipment such as computers and printers fluorescent lighting battery chargers and also variable speed drives Electric motors do not normally contribute significantly to harmonic generation Both motors and transformers will however create harmonics when they are over fluxed or saturated Non linear load currents create distortion in the pure sinusoidal voltage waveform supplied by the utility and this may result in resonance The even harmonics do not normally exist in power system due to symmetry between the positive and negative halves of a cycle Further if the waveforms of the three phases are symmetrical the harmonic multiples of three are suppressed by delta D connection of transformers and motors as described below If we focus for example on only the third harmonic we can see how all harmonics with a multiple of three behaves in powers systems 2 nbsp 3rd Order Harmonic Addition Power is supplied by a three phase system where each phase is 120 degrees apart This is done for two reasons mainly because three phase generators and motors are simpler to construct due to constant torque developed across the three phase phases and secondly if the three phases are balanced they sum to zero and the size of neutral conductors can be reduced or even omitted in some cases Both these measures results in significant costs savings to utility companies However the balanced third harmonic current will not add to zero in the neutral As seen in the figure the 3rd harmonic will add constructively across the three phases This leads to a current in the neutral wire at three times the fundamental frequency which can cause problems if the system is not designed for it i e conductors sized only for normal operation 2 To reduce the effect of the third order harmonics delta connections are used as attenuators or third harmonic shorts as the current circulates in the delta the connection instead of flowing in the neutral of a Y D transformer wye connection nbsp A compact fluorescent lamp is one example of an electrical load with a non linear characteristic due to the rectifier circuit it uses The current waveform blue is highly distorted Voltage harmonics editVoltage harmonics are mostly caused by current harmonics The voltage provided by the voltage source will be distorted by current harmonics due to source impedance If the source impedance of the voltage source is small current harmonics will cause only small voltage harmonics It is typically the case that voltage harmonics are indeed small compared to current harmonics For that reason the voltage waveform can usually be approximated by the fundamental frequency of voltage If this approximation is used current harmonics produce no effect on the real power transferred to the load An intuitive way to see this comes from sketching the voltage wave at fundamental frequency and overlaying a current harmonic with no phase shift in order to more easily observe the following phenomenon What can be observed is that for every period of voltage there is equal area above the horizontal axis and below the current harmonic wave as there is below the axis and above the current harmonic wave This means that the average real power contributed by current harmonics is equal to zero However if higher harmonics of voltage are considered then current harmonics do make a contribution to the real power transferred to the load A set of three line or line to line voltages in a balanced three phase three wire or four wire power system cannot contain harmonics whose frequency is an integer multiple of the frequency of the third harmonics i e harmonics of order h 3 n displaystyle h 3n nbsp which includes triplen harmonics i e harmonics of order h 3 2 n 1 displaystyle h 3 2n 1 nbsp 3 This occurs because otherwise Kirchhoff s voltage law KVL would be violated such harmonics are in phase so their sum for the three phases is not zero however KVL requires the sum of such voltages to be zero which requires the sum of such harmonics to be also zero With the same argument a set of three line currents in a balanced three wire three phase power system cannot contain harmonics whose frequency is an integer multiple of the frequency of the third harmonics but a four wire system can and the triplen harmonics of the line currents would constitute the neutral current Even odd triplen and non triplen odd harmonics editThe harmonics of a distorted non sinusoidal periodic signal can be classified according to their order The cyclic frequency in hertz of the harmonics are usually written as f n displaystyle f n nbsp or f h displaystyle f h nbsp and they are equal to n f 0 displaystyle nf 0 nbsp or h f 0 displaystyle hf 0 nbsp where n displaystyle n nbsp or h displaystyle h nbsp is the order of the harmonics which are integer numbers and f 0 displaystyle f 0 nbsp is the fundamental cyclic frequency of the distorted non sinusoidal periodic signal Similarly the angular frequency in radians per second of the harmonics are written as w n displaystyle omega n nbsp or w h displaystyle omega h nbsp and they are equal to n w 0 displaystyle n omega 0 nbsp or h w 0 displaystyle h omega 0 nbsp where w 0 displaystyle omega 0 nbsp is the fundamental angular frequency of the distorted non sinusoidal periodic signal The angular frequency is related to the cyclic frequency as w 2 p f displaystyle omega 2 pi f nbsp valid for harmonics as well as the fundamental component Even harmonics edit The even harmonics of a distorted non sinusoidal periodic signal are harmonics whose frequency is a non zero even integer multiple of the fundamental frequency of the distorted signal which is the same as the frequency of the fundamental component So their order is given by h 2 k k N even harmonics displaystyle h 2k quad k in mathbb N quad text even harmonics nbsp where k displaystyle k nbsp is an integer number for example h 2 4 6 8 10 displaystyle h 2 4 6 8 10 nbsp If the distorted signal is represented in the trigonometric form or the amplitude phase form of the Fourier series then k displaystyle k nbsp takes only positive integer values not including zero that is it takes values from the set of natural numbers if the distorted signal is represented in the complex exponential form of the Fourier series then k displaystyle k nbsp takes negative and positive integer values not including zero since the DC component is usually not considered as a harmonic Odd harmonics edit The odd harmonics of a distorted non sinusoidal periodic signal are harmonics whose frequency is an odd integer multiple of the fundamental frequency of the distorted signal which is the same as the frequency of the fundamental component So their order is given by h 2 k 1 k N odd harmonics displaystyle h 2k 1 quad k in mathbb N quad text odd harmonics nbsp for example h 1 3 5 7 9 displaystyle h 1 3 5 7 9 nbsp In distorted periodic signals or waveforms that possess half wave symmetry which means the waveform during the negative half cycle is equal to the negative of the waveform during the positive half cycle all of the even harmonics are zero a 2 k b 2 k A 2 k 0 displaystyle a 2k b 2k A 2k 0 nbsp and the DC component is also zero a 0 0 displaystyle a 0 0 nbsp so they only have odd harmonics A 2 k 1 0 displaystyle A 2k 1 neq 0 nbsp these odd harmonics in general are cosine terms as well as sine terms but in certain waveforms such as square waves the cosine terms are zero a 2 k 1 0 displaystyle a 2k 1 0 nbsp b 2 k 1 0 displaystyle b 2k 1 neq 0 nbsp In many non linear loads such as inverters AC voltage controllers and cycloconverters the output voltage s waveform s usually has half wave symmetry and so it only contains odd harmonics The fundamental component is an odd harmonic since when k 1 displaystyle k 1 nbsp the above formula yields h 1 displaystyle h 1 nbsp which is the order of the fundamental component If the fundamental component is excluded from the odd harmonics then the order of the remaining harmonics is given by h 2 k 1 k N odd harmonics that aren t the fundamental displaystyle h 2k 1 quad k in mathbb N quad text odd harmonics that aren t the fundamental nbsp for example h 3 5 7 9 11 displaystyle h 3 5 7 9 11 nbsp Triplen harmonics edit The triplen harmonics of a distorted non sinusoidal periodic signal are harmonics whose frequency is an odd integer multiple of the frequency of the third harmonic s of the distorted signal So their order is given by h 3 2 k 1 k N triplen harmonics displaystyle h 3 2k 1 quad k in mathbb N quad text triplen harmonics nbsp for example h 3 9 15 21 27 displaystyle h 3 9 15 21 27 nbsp All triplen harmonics are also odd harmonics but not all odd harmonics are also triplen harmonics Non triplen odd harmonics edit It is a Certain distorted non sinusoidal periodic signals only possess harmonics that are neither even nor triplen harmonics for example the output voltage of a three phase wye connected AC voltage controller with phase angle control and a firing angle of a 45 displaystyle alpha 45 circ nbsp and with a purely resistive load connected to its output and fed with three phase sinusoidal balanced voltages Their order is given by h 1 2 6 k 1 k 3 k N non triplen odd harmonics displaystyle h frac 1 2 6 k 1 k 3 quad k in mathbb N quad text non triplen odd harmonics nbsp for example h 1 5 7 11 13 17 19 23 25 displaystyle h 1 5 7 11 13 17 19 23 25 nbsp All harmonics that are not even harmonics nor triplen harmonics are also odd harmonics but not all odd harmonics are also harmonics that are not even harmonics nor triplen harmonics If the fundamental component is excluded from the harmonics that are not even nor triplen harmonics then the order of the remaining harmonics is given by h 1 2 1 k 6 k 1 k 3 1 k 1 k N non triplen odd harmonics that aren t the fundamental displaystyle h frac 1 2 1 k 6 k 1 k 3 1 k 1 quad k in mathbb N quad text non triplen odd harmonics that aren t the fundamental nbsp or also by h 6 k 1 k N non triplen odd harmonics that aren t the fundamental displaystyle h 6k mp 1 quad k in mathbb N quad text non triplen odd harmonics that aren t the fundamental nbsp for example h 5 7 11 13 17 19 23 25 displaystyle h 5 7 11 13 17 19 23 25 nbsp In this latter case these harmonics are called by IEEE as nontriple odd harmonics 4 Positive sequence negative sequence and zero sequence harmonics editIn the case of balanced three phase systems three wire or four wire the harmonics of a set of three distorted non sinusoidal periodic signals can also be classified according to their phase sequence 5 7 8 6 3 Positive sequence harmonics edit The positive sequence harmonics of a set of three phase distorted non sinusoidal periodic signals are harmonics that have the same phase sequence as that of the three original signals and are phase shifted in time by 120 between each other for a given frequency or order 7 It can be proven the positive sequence harmonics are harmonics whose order is given by h 3 k 2 k N positive sequence harmonics displaystyle h 3k 2 quad k in mathbb N quad text positive sequence harmonics nbsp for example h 1 4 7 10 13 displaystyle h 1 4 7 10 13 nbsp 6 3 The fundamental components of the three signals are positive sequence harmonics since when k 1 displaystyle k 1 nbsp the above formula yields h 1 displaystyle h 1 nbsp which is the order of the fundamental components If the fundamental components are excluded from the positive sequence harmonics then the order of the remaining harmonics is given by 5 h 3 k 1 k N positive sequence harmonics that aren t the fundamentals displaystyle h 3k 1 quad k in mathbb N quad text positive sequence harmonics that aren t the fundamentals nbsp for example h 4 7 10 13 16 displaystyle h 4 7 10 13 16 nbsp Negative sequence harmonics edit The negative sequence harmonics of a set of three phase distorted non sinusoidal periodic signals are harmonics that have an opposite phase sequence to that of the three original signals and are phase shifted in time by 120 for a given frequency or order 7 It can be proven the negative sequence harmonics are harmonics whose order is given by 5 h 3 k 1 k N negative sequence harmonics displaystyle h 3k 1 quad k in mathbb N quad text negative sequence harmonics nbsp for example h 2 5 8 11 14 displaystyle h 2 5 8 11 14 nbsp 6 3 Zero sequence harmonics edit The zero sequence harmonics of a set of three phase distorted non sinusoidal periodic signals are harmonics that are in phase in time for a given frequency or order It can be proven the zero sequence harmonics are harmonics whose frequency is an integer multiple of the frequency of the third harmonics 5 So their order is given by h 3 k k N zero sequence harmonics displaystyle h 3k quad k in mathbb N quad text zero sequence harmonics nbsp for example h 3 6 9 12 15 displaystyle h 3 6 9 12 15 nbsp 6 3 All triplen harmonics are also zero sequence harmonics 5 but not all zero sequence harmonics are also triplen harmonics Total harmonic distortion editTotal harmonic distortion or THD is a common measurement of the level of harmonic distortion present in power systems THD can be related to either current harmonics or voltage harmonics and it is defined as the ratio of the RMS value of all harmonics to the RMS value of the fundamental component times 100 the DC component is neglected T H D V V 2 2 V 3 2 V 4 2 V n 2 V 1 100 k 2 n V k 2 V 1 100 displaystyle mathit THD V frac sqrt V 2 2 V 3 2 V 4 2 cdots V n 2 V 1 cdot 100 frac sqrt sum k mathop 2 n V k 2 V 1 cdot 100 nbsp T H D I I 2 2 I 3 2 I 4 2 I n 2 I 1 100 k 2 n I k 2 I 1 100 displaystyle THD I frac sqrt I 2 2 I 3 2 I 4 2 cdots I n 2 I 1 cdot 100 frac sqrt sum k mathop 2 n I k 2 I 1 cdot 100 nbsp where Vk is the RMS voltage of the kth harmonic Ik is the RMS current of the kth harmonic and k 1 is the order of the fundamental component It is usually the case that we neglect higher voltage harmonics however if we do not neglect them real power transferred to the load is affected by harmonics Average real power can be found by adding the product of voltage and current and power factor denoted by pf here at each higher frequency to the product of voltage and current at the fundamental frequency or P avg k 1 V k I k p f P avg 1 P avg 2 displaystyle P text avg sum k mathop 1 infty V k cdot I k cdot pf P text avg 1 P text avg 2 cdots nbsp where Vk and Ik are the RMS voltage and current magnitudes at harmonic k k 1 displaystyle k 1 nbsp denotes the fundamental frequency and P avg 1 displaystyle P text avg 1 nbsp is the conventional definition of power without factoring in harmonic components The power factor mentioned above is the displacement power factor There is another power factor that depends on THD True power factor can be taken to mean the ratio between average real power and the magnitude of RMS voltage and current p f true P avg V rms I rms displaystyle pf text true frac P text avg V text rms I text rms nbsp 8 V rms V 1 rms 1 T H D V 100 2 displaystyle V text rms V 1 text rms sqrt 1 left frac THD V 100 right 2 nbsp and I rms I 1 rms 1 T H D I 100 2 displaystyle I text rms I 1 text rms sqrt 1 left frac THD I 100 right 2 nbsp Substituting this in for the equation for true power factor it becomes clear that the quantity can be taken to have two components one of which is the traditional power factor neglecting the influence of harmonics and one of which is the harmonics contribution to power factor p f true P avg V 1 rms I 1 rms 1 1 T H D V 100 2 1 T H D I 100 2 displaystyle pf text true frac P text avg V 1 text rms I 1 text rms cdot frac 1 sqrt 1 left frac THD V 100 right 2 sqrt 1 left frac THD I 100 right 2 nbsp Names are assigned to the two distinct factors as follows p f true p f disp p f dist displaystyle pf text true pf text disp cdot pf text dist nbsp where p f disp displaystyle pf text disp nbsp is the displacement power factor and p f dist displaystyle pf text dist nbsp is the distortion power factor i e the harmonics contribution to total power factor Effects editOne of the major effects of power system harmonics is to increase the current in the system This is particularly the case for the third harmonic which causes a sharp increase in the zero sequence current and therefore increases the current in the neutral conductor This effect can require special consideration in the design of an electric system to serve non linear loads 9 In addition to the increased line current different pieces of electrical equipment can suffer effects from harmonics on the power system Motors edit Electric motors experience losses due to hysteresis and eddy currents set up in the iron core of the motor These are proportional to the frequency of the current Since the harmonics are at higher frequencies they produce higher core losses in a motor than the power frequency would This results in increased heating of the motor core which if excessive can shorten the life of the motor The 5th harmonic causes a CEMF counter electromotive force in large motors which acts in the opposite direction of rotation The CEMF is not large enough to counteract the rotation however it does play a small role in the resulting rotating speed of the motor Telephones edit In the United States common telephone lines are designed to transmit frequencies between 300 and 3400 Hz Since electric power in the United States is distributed at 60 Hz it normally does not interfere with telephone communications because its frequency is too low Sources editA pure sinusoidal voltage is a conceptual quantity produced by an ideal AC generator built with finely distributed stator and field windings that operate in a uniform magnetic field Since neither the winding distribution nor the magnetic field are uniform in a working AC machine voltage waveform distortions are created and the voltage time relationship deviates from the pure sine function The distortion at the point of generation is very small about 1 to 2 but nonetheless it exists Because this is a deviation from a pure sine wave the deviation is in the form of a periodic function and by definition the voltage distortion contains harmonics When a sinusoidal voltage is applied to a linear time invariant load such as a heating element the current through it is also sinusoidal In non linear and or time variant loads such as an amplifier with a clipping distortion the voltage swing of the applied sinusoid is limited and the pure tone is polluted with a plethora of harmonics When there is significant impedance in the path from the power source to a nonlinear load these current distortions will also produce distortions in the voltage waveform at the load However in most cases where the power delivery system is functioning correctly under normal conditions the voltage distortions will be quite small and can usually be ignored Waveform distortion can be mathematically analysed to show that it is equivalent to superimposing additional frequency components onto a pure sinewave These frequencies are harmonics integer multiples of the fundamental frequency and can sometimes propagate outwards from nonlinear loads causing problems elsewhere on the power system The classic example of a non linear load is a rectifier with a capacitor input filter where the rectifier diode only allows current to pass to the load during the time that the applied voltage exceeds the voltage stored in the capacitor which might be a relatively small portion of the incoming voltage cycle Other examples of nonlinear loads are battery chargers electronic ballasts variable frequency drives and switching mode power supplies See also editPower factorFurther reading editSankaran C 1999 10 01 Effects of Harmonics on Power Systems Electrical Construction and Maintenance Magazine Penton Media Inc Retrieved 2020 03 11 References edit Das J C 2015 Power System Harmonics and Passive Filter Design Wiley IEEE Press ISBN 978 1 118 86162 2 To distinguish between linear and nonlinear loads we may say that linear time invariant loads are characterized so that an application of a sinusoidal voltage results in a sinusoidal flow of current a b Harmonics Made Simple ecmweb com Retrieved 2015 11 25 a b c d e Wakileh George J 2001 Power Systems Harmonics Fundamentals Analysis and Filter Design 1 ed Springer pp 13 15 ISBN 978 3 642 07593 3 IEEE Standard 519 IEEE recommended practices and requirements for harmonic control in electric power systems IEEE 519 1992 p 10 a b c d e Das J C 2015 Power System Harmonics and Passive Filter Design Wiley IEEE Press ISBN 978 1 118 86162 2 To distinguish between linear and nonlinear loads we may say that linear time invariant loads are characterized so that an application of a sinusoidal voltage results in a sinusoidal flow of current a b c d Fuchs Ewald F Masoum Mohammad A S 2008 Power Quality in Power Systems and Electrical Machines 1 ed Academic Press pp 17 18 ISBN 978 0123695369 a b Santoso Surya Beaty H Wayne Dugan Roger C McGranaghan Mark F 2003 Electrical Power Systems Quality 2 ed McGraw Hill p 178 ISBN 978 0 07 138622 7 W Mack Grady and Robert Gilleski Harmonics and How They Relate to Power Factor PDF Proc of the EPRI Power Quality Issues amp Opportunities Conference For example see the National Electrical Code A 3 phase 4 wire wye connected power system used to supply power to nonlinear loads may necessitate that the power system design allow for the possibility of high harmonic neutral currents Article 220 61 C FPN No 2 Retrieved from https en wikipedia org w index php title Harmonics electrical power amp oldid 1220854732, wikipedia, wiki, book, books, library,

article

, read, download, free, free download, mp3, video, mp4, 3gp, jpg, jpeg, gif, png, picture, music, song, movie, book, game, games.